Plan Review Notes
Plan Review Notes For Permit 08060702
Permit Number 08060702
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-03 10:01:51 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.NOTE SAME ON THE PLAN.
  
 2} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER
 REQUIRED BY 61G15-23.002FLORIDA ADMINISTRATIVE CODE.
  
 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 4} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718