| Plan Review Notes For Permit 08060702 |
| Permit Number |
08060702 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-03 10:01:51 | | | | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE | | | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE | | | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE | | | ARTICLE.NOTE SAME ON THE PLAN. | | | | | | 2} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL | | | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER | | | REQUIRED BY 61G15-23.002FLORIDA ADMINISTRATIVE CODE. | | | | | | 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. | | | | | | 4} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN | | | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE | | | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE | | | PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|