2008-07-28 11:31:47PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: THERE WERE NO COMMET RESPONSES FROM THE DESIGNER
 AND NONE OF THE PREVIOUS PLUMBING REVIEW COMMENTS WERE
 ADDRESSED
  
 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN OF SHEET A1 AND IS NOT CODE
 COMPLIANT PER FBC- PLUMBING THE FOLLOWING SECTIONS.
  
 A} BATHTUB MISSING FROM RISER DIAGRAM. PER SECTIONS
 401.1 AND 701.1 SCOPE.
  
 B} BOTH SINKS IN THE KITCHEN REQUIRE VENTS. PER
 SECTION 901.2.1 VENTING REQUIRED.
  
 C} SINK IN THE LAUNDRY REQUIRES A VENT. PER 901.2.1
 VENTING REQUIRED.
  
 D} THE WASHING MACHINE IS DESIGNED WITH A PROHIBITED
 "S" TRAP. PER SECTION 1002.3 PROHIBITED TRAPS (5). THE
 WASHING MACHINE REQUIRES A VENT. PER SECTION 901.2.1
 VENTING REQUIRED.
 NOTE: PLEASE DESIGN THE WASHING MACHINE PER THE
 FOLLOWING.
  
 SECTION 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE
 DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 SECTION 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 NOTE: CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE
 WASHING MACHINE.
  
 SECTION 708.7 MINIMUM SIZE. CLEANOUTS SHALL BE THE
 SAME NOMINAL SIZE AS THE PIPE THEY SERVE UP TO 4 INCHES
 (102MM)
 NOTE: WASHING MACHINE CLEANOUT SHALL BE 3".
  
 SECTION 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: WASHING MACHINE CLEANOUT SHALL BE LOCATED AT 4'
 A.F.F.
  
 E} "OK" COMMENT ADDRESSED.
  
 2. SHEET A1 NEW FLOOR PLAN INDCATES ICE. IS THIS AN
 ICE MAKER? NOTE: THE ICE MAKER MAY REQUIRE A DRAIN PIPE
 FROM THE SANITARY SYSTEM. PLEASE SUBMIT TWO COPIES OF
 ICE MAKER MANUFACTURE SHEETS AND DESIGN SANITARY SYSTEM
 ACCORDINGLY IF A DRAIN IS REQUIRED. PER FBC- PLUMBING
 SECTION 701.1 SCOPE. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. PER FBC- PLUMBING SECTION 1002.4 TRAP
 SEALS.
  
 **THE FOLLOWING ARE NEW COMMENTS
  
 3. SHEET A1 SCOPE OF WORK INDICATES IN THE GUEST
 BEDROOM (NEW MASTER CLOSET) ADD DRAINS AND CAP FOR
 SINKS (FUTURE APPLICATION) AND ADD WC WASTE LINE AND
 CAP (FUTURE USE). THESE FUTURE FIXTURES AND LAYOUT MUST
 BE INDICATED ON THE PROPOSED NEW FLOOR PLAN AND THE
 SANITARY WASTE, VENTS, TRAPS AND CLEANOUTS WITH SIZES
 MUST BE CLEALY INDICATED ON THE SANITARY RISER DIAGRAM
 FOR THESE FUTURE FIXTURES ON SHEET A3. PER (W.P.B. AS
 AMENDED) SECTION 106.3.5.4(9) PLUMBING AND FBC-2004
 PLUMBING SECTION 701.1, AND SECTION 901.1 SCOPE.
  
 4. SHEET A1 INDICATES GAS APPLIANCES (GAS W.H.& GAS
 RANGE): PLEASE KNOW THAT A GAS PERMIT IS REQUIRED FOR
 THIS WORK. A LICENSED GAS OR PLUMBING CONTRACTOR SHALL
 SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS
 INSPECTIONS ARE TO BE COMPLETE BEFORE THE FINAL
 INSPECTION.
  
 5. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]