| 2008-07-22 10:47:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | |
| | 1) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR |
| | PLAN SHOWS A GAS WATER HEATER (APPEARS TO BE A |
| | TANKLESS) IN THE NEW STORAGE ROOM. THIS APPEARS TO BE A |
| | CONFINED SPACE, PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS |
| | WATER HEATER AND STATE WERE IT'S GETTING THE COMBUSTION |
| | AIR FROM, IF NOT A GAS WATER HEATER CORRECT PLANS PAGES |
| | A1 AND A2, PER 2004 FBC/R G2407.1. |
| | |
| | 2) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR |
| | PLAN SHOWS THE AIR HANDLER BEING RELOCATED TO THE NEW |
| | A/C CLOSET, PLEASE SUBMIT A MECHANICAL PLAN SHOWING THE |
| | SUPPLY AND RETURN AIR DUCTS THAT ARE BEING ALTERED, PER |
| | 2004 FBC/R M1601.1. |
| | |
| | 3) AS NOTED IN LAST REVIEW 6-25-08. PLAN A2 ELECTRICAL |
| | PLAN IS LABELING THE A/C CONDENSER UNITS AS A.H.U. (AIR |
| | HANDLER UNIT), PLEASE CORRECT PER 2004 FBC/R, CH. 13 |
| | ANDFBC 106.1.1. |
| | |
| | 4) PLAN A1 AND A2 SHOW A A/C CONDENSER UNIT LABELED |
| | FUTURE AHU, PLEASE REMOVE FROM PLANS OR SHOW THE |
| | COMPLETE SYSTEM IT IS GOING TO, PER 2004 WPB AMEND. |
| | 106.3.5.4 (10). |
| | |
| | 5) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, SEE F.B.C. 106.1.1. |
| | |
| | 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR |
| | TIMES THE FEE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |