2008-07-22 10:47:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR
 PLAN SHOWS A GAS WATER HEATER (APPEARS TO BE A
 TANKLESS) IN THE NEW STORAGE ROOM. THIS APPEARS TO BE A
 CONFINED SPACE, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS
 WATER HEATER AND STATE WERE IT'S GETTING THE COMBUSTION
 AIR FROM, IF NOT A GAS WATER HEATER CORRECT PLANS PAGES
 A1 AND A2, PER 2004 FBC/R G2407.1.
  
 2) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR
 PLAN SHOWS THE AIR HANDLER BEING RELOCATED TO THE NEW
 A/C CLOSET, PLEASE SUBMIT A MECHANICAL PLAN SHOWING THE
 SUPPLY AND RETURN AIR DUCTS THAT ARE BEING ALTERED, PER
 2004 FBC/R M1601.1.
  
 3) AS NOTED IN LAST REVIEW 6-25-08. PLAN A2 ELECTRICAL
 PLAN IS LABELING THE A/C CONDENSER UNITS AS A.H.U. (AIR
 HANDLER UNIT), PLEASE CORRECT PER 2004 FBC/R, CH. 13
 ANDFBC 106.1.1.
  
 4) PLAN A1 AND A2 SHOW A A/C CONDENSER UNIT LABELED
 FUTURE AHU, PLEASE REMOVE FROM PLANS OR SHOW THE
 COMPLETE SYSTEM IT IS GOING TO, PER 2004 WPB AMEND.
 106.3.5.4 (10).
  
 5) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  