Plan Review Notes For Permit 08060680
Permit Number 08060680
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-22 08:38:38 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE FROM THE PREVIOUS REVIEW AND
 HAD INCORRECT OR NO RESPONSE.
  
 1} THE 250 MCM CONDUCTORS FEEDING THE 400 AMP MDP DO
 NOT COMPLY WITH 310.15(B)(6), NEED TO BE A MINIMUM OF
 400 MCM FOR A 400 AMP SERVICE. NOTE: THE MAIN IS 200
 AMP AND THE NOTE ON THE CALCULATIONS INDICATE A 200 AMP
 SERVICE. CORRELATE THE RISER.***THERE ARE 250 MCM
 FEDING THE 200 AMP MAIN AND NOW 400 MCM FEEDING THE
 "MDP" WHICH IS ALSO RATED AT 200 AMPS.THE 400 MCM
 THOUGH NOT A VIOLATION, MUST BE INSTALLED IF THE
 DESIGNER CHOOSES TO USE THEM. A REVISION WILL BE
 REQUIRED TO CHANGE THE PLAN IN THE FUTURE.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.WHERE IS THE MDP LOCATED ?*** STILL NOT SHOWN
 ON THE PLAN.
  
 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).***ONLY ONE AHU IS SHOWN AND TWO COMPRESSERS.PLEASE
 CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718