2008-06-25 13:46:28***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 FRONT TRELLIS/WALL STRUCTURE TO ALL ADJACENT PROPERTY
 LINES.
  
 2)CLARIFY SCOPE OF WORK.SOME DETAILS INDICATE THE
 EASTERN PRIVACY WALL IS FUTURE WORK, OTHERS (SOUTH
 ELEVATIONS ON SHEET A3) SHOW THE WALL AS "NEW WALL". IS
 THIS STRUCTURE TO BE INCLUDED IN THIS SCOPE OF WORK OR
 NOT?IF INCLUDED, INDICATE THE DIMENSION FROM THE
 PROPERTY LINE AT WHICH THE WALL EXCEEDS 6 FEET IN
 HEIGHT.
 NOTE:WALLS/FENCES SHALL NOT EXCEED 6' IN HEIGHT
 WITHIN THE REQUIRED SIDE/REAR SETBACK.
 NOTE:THE HEIGHT DIMENSIONS OF THIS WALL STRUCTURE DO
 NOT MATCH BETWEEN NORTH AND SOUTH ELEVATIONS.
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL ADJACENT PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 NOTE:ANY MECHANICAL EQUIPMENT ("FUTURE GENERATOR") IS
 REQUIRED TO BE SETBACK A MINIMUM OF 5.1 FEET FROM THE
 EASTERN SIDE PROPERTY LINE PURSUANT TO THE
 AFOREMENTIONED CODE SECTION.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
 SENT TO "E" - SF RACK