| 2008-07-02 10:35:39 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN OF SHEET A1 AND IS NOT CODE |
| | COMPLIANT PER FBC- PLUMBING THE FOLLOWING SECTIONS. |
| | |
| | A} BATHTUB MISSING FROM RISER DIAGRAM. PER SECTIONS |
| | 401.1 AND 701.1 SCOPE. |
| | |
| | B} BOTH SINKS IN THE KITCHEN REQUIRE VENTS. PER |
| | SECTION 901.2.1 VENTING REQUIRED. |
| | |
| | C} SINK IN THE LAUNDRY REQUIRES A VENT. PER 901.2.1 |
| | VENTING REQUIRED. |
| | |
| | D} THE WASHING MACHINE IS DESIGNED WITH A PROHIBITED |
| | "S" TRAP. PER SECTION 1002.3 PROHIBITED TRAPS (5). THE |
| | WASHING MACHINE REQUIRES A VENT. PER SECTION 901.2.1 |
| | VENTING REQUIRED. |
| | NOTE: PLEASE DESIGN THE WASHING MACHINE PER THE |
| | FOLLOWING. |
| | |
| | SECTION 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE |
| | DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | SECTION 802.4 STANDPIPES.STANDPIPES SHALL BE |
| | INDIVIDUALLY TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | NOTE: CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE |
| | WASHING MACHINE. |
| | |
| | SECTION 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | NOTE: WASHING MACHINE CLEANOUT SHALL BE 3". |
| | |
| | SECTION 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | NOTE: WASHING MACHINE CLEANOUT SHALL BE LOCATED AT 4' |
| | A.F.F. |
| | |
| | E} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF |
| | THE BUILDING DRAIN AND BUILDING SEWER AS BEING A |
| | TWO-WAY CLEANOUT. PER SECTION 708.3.5. |
| | |
| | NOTE: PLEASE REFERENCE THE SANITARY ISOMETRIC EXAMPLE |
| | THAT REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT |
| | ATTACHED TO THESE PLUMBING COMMENTS FOR REFERENCE TO |
| | ASSIST IN THE RESUBMITTAL. |
| | |
| | 2. SHEET A1 NEW FLOOR PLAN INDCATES ICE. IS THIS AN |
| | ICE MAKER? NOTE: THE ICE MAKER MAY REQUIRE A DRAIN PIPE |
| | FROM THE SANITARY SYSTEM. PLEASE SUBMIT TWO COPIES OF |
| | ICE MAKER MANUFACTURE SHEETS AND DESIGN SANITARY SYSTEM |
| | ACCORDINGLY IF A DRAIN IS REQUIRED. PER FBC- PLUMBING |
| | SECTION 701.1 SCOPE. WHERE A TRAP SEAL IS SUBJECT TO |
| | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. PER FBC- PLUMBING SECTION 1002.4 TRAP |
| | SEALS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |