Plan Review Notes
Plan Review Notes For Permit 08060680
Permit Number 08060680
Review Stop M
Sequence Number 1
Notes
Date Text
2008-06-25 14:56:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT A MECHANICAL (A/C) PLAN, PER 2004 WPB
 AMEND. 106.3.5.4 (10).
  
 2) PLAN A1 NEW FLOOR PLAN SHOWS A GAS WATER HEATER
 (APPEARS TO BE A TANKLESS) IN THE NEW STORAGE ROOM.
 THIS APPEARS TO BE A CONFINED SPACE, PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS WATER HEATER AND STATE WERE IT'S
 GETTING THE COMBUSTION AIR FROM, PER 2004 FBC/R
 G2407.1.
  
 3) PLAN A1 NEW FLOOR PLAN SHOWS THE AIR HANDLER BEING
 RELOCATED TO THE NEW A/C CLOSET, PLEASE SHOW ON THE NEW
 MECHANICAL PLAN BEING SUBMITTED THE SUPPLY AND RETURN
 AIR DUCTS, PER 2004 FBC/R M1601.1.
  
 4) PLAN A2 TOTAL BUILDING LOAD CALCULATIONS STATES THE
 CLOTHES DRYER IS GAS, THE ELECTRICAL PLAN SHOWS A 220V
 OUTLET FOR IT. PLEASE CLARIFY ON THE PLANS IF THE
 CLOTHES DRYER IS GAS OR ELECTRIC, PER 2004 FBC/R
 G2407.1 AND FBC 106.1.1.
  
 5) PLAN A2 ELECTRICAL PLAN IS LABELING THE A/C
 CONDENSER UNITS AS A.H.U. (AIR HANDLER UNIT), PLEASE
 CORRECT PER 2004 FBC/R, CH. 13 ANDFBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;