| 2008-08-20 17:10:00 | BUILDING PLAN REVIEW |
| | PERMIT: 08060669 |
| | ADD: 400 N. FLAGLER DR. #605 |
| | CONT: HAWKES & DANIEL CONSTRUCTION |
| | TEL: (561)315-2525 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)OK |
| | |
| | **NO COMMENT NOT ADDRESSED** |
| | 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | NO INFORMATION WAS SUBMITTED FOR THE SOFFITS. ELEVATION |
| | DETAILS REQUIRED. WHAT IS THE NEW OPENING DIMENSIONS? |
| | 5)PROVIDE ELEVATION DETAILED ARCHITECTURAL DRAWINGS |
| | TO CLEARLY SHOW THE WORK. WILL BE SOFFIT BE INSTALLED |
| | THROUGHOUT THE SPACE?SUBMIT THE FRAMING DETAILS FOR |
| | THE NEW WALLS AND SOFFITS SHOWING THE STRUCTURAL |
| | ATTACHMENTS AND ALL MATERIALS. |
| | |
| | 6)OK |
| | 7)OK |
| | 8)OK. |
| | 9)OK |
| | |
| | **NO COMMENT NOT ADDRESSED** |
| | 10) 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING |
| | UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR |
| | SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 492. PROVIDE INFORMATION MEETING THIS REQUIREMENT OR |
| | INDICATE ON THE PLANS THE TYPE OF CORK WHICH WILL BE |
| | USED UNDER THE TILES. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |