| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | SECTION 611 (EXISTING BIDING CODE). |
| | ENERGY CONSERVATION |
| | 611.1MINIMUM REQUIREMENTS. |
| | ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH |
| | THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 1}PER CHAPTER 13 FBC, SUBCHAPTER 13-400.0.C.4, |
| | PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER |
| | 13-415.2. SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES |
| | ON THE PLAN TO CORRELATE WITH THE ONES IN THE |
| | CALCULATIONS.THIS PRESCRIPTIVE METHOD CAN BE SHOWN ON |
| | THE ELECTRICAL PLAN |
| | |
| | 2} 13-415.1.ABC.1.2 SPACE CONTROL. |
| | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A |
| | CONTROL DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY |
| | TURNS LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS |
| | LEAVING A SPACE, EXCEPT SPACES WITH MULTISCENE CONTROL, |
| | IN THE FOLLOWING: 1. CLASSROOMS (NOT INCLUDING SHOP |
| | CLASSROOMS, LABORATORY CLASSROOMS, AND PRESCHOOL |
| | THROUGH 12TH GRADE CLASSROOMS). 2. CONFERENCE/MEETING |
| | ROOMS. |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | INDICATE COMPLIANCE WITH THESE SECTIONS ON THE PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |