| 2008-07-01 15:40:10 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1 DECLARE THE GOVERNING CODE. (FBC-2004 |
| | WITH 2007 REVISIONS). PER (W.P.B. AS AMENDED) SECTION |
| | 106.5 RETENTION OF CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SHEET A-1 DEMOLITION PLAN: PLEASE ADD THE FOLLOWONG |
| | TO NOTES, PER FBC-2004 W/07 REV. PLUMBING, SECTION |
| | 704.5 DEAD ENDS: IN THE REMOVAL OF ANY PART OF A |
| | DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A |
| | PLUMBING PERMIT IS REQUIRED AND AN INSPECTION IS |
| | REQUIRED OF THE PLUMBING DEMO WORK PRIOR TO COVERING |
| | THE DEMO WORK WITH FINNISH WALLS, CIELINGS, OR POURED |
| | CONCRETE SLABS. |
| | |
| | 3. SHEET MEP-1 IS IDENTIFIED WRONG AS SHEET MEP-2 PER |
| | THE SHEET INDEX ON SHEET A-1. PER (W.P.B. AS AMENDED) |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. SHEET MEP-1 SANITARY RISER DIAGRAM: THE SHOWER |
| | REQUIRES A VENT. PER FBC- PLUMBING SECTION 901.2.1 |
| | VENTING REQUIRED. |
| | |
| | 5. SHEET MEP-1 PLUMBING NOTE #11: AIR CHAMBERS OR |
| | SHOCK ABSORBERS ARE NOT APPROVED BY THE FBC- PLUMBING |
| | SECTION 604.9 WATER HAMMER. PLEASE DELETE AIR CHAMBER |
| | AND SHOCK ABSORBER FROM NOTE #11 AND ADD IN THEIR PLACE |
| | THE FOLLOWING "WATER-HAMMER ARRESTORS". |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |