| Plan Review Notes For Permit 08060641 |
| Permit Number |
08060641 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-24 09:57:13 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. | | | | | | 2} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE | | | COMPLIANCE ON THE PLAN, A NOTE WILL BE SUFFICIENT FOR | | | AREAS NOT SHOWN ON THE PLAN, LOCATE THE ALARMS IN THOSE | | | AREAS REQUIRED ON THE SUBMITTED FLOOR PLAN. | | | | | | NOTE: AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS | | | AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|