| Date |
Text |
| 2008-07-09 11:29:47 | BUILDING PLAN REVIEW |
| | PERMIT: 08060628 |
| | ADD: 1201 N. OLIVE AVE |
| | CONT: ANDERSON-MOORE CONSTRUCTION |
| | TEL: (561)753-7400 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 7-9-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS THAT |
| | ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVAL |
| | FOR THE NEW EXTERIOR DOOR. |
| | |
| | 5) FOR CLARITY PROVIDE AN EXISTING FLOOR PLAN SHOWING |
| | ALL WALLS, DOORS, WINDOWS AND ANY OTHER SYSTEMS LOCATED |
| | IN THE AREA WHICH WILL BE DEMOED: THEN, THE PROPOSED |
| | PLAN NEEDS TO CLEARLY SHOW ALL NEW SYSTEMS AND DOORS |
| | WHICH WILL BE INSTALLED AND THE HOW THE ROOM WILL BE |
| | LAID OUT WHEN FINISHED. SHEET 3.1 HAS SOME OF THIS |
| | INFORMATION HOWEVER, I AM NOT SURE IF THE NEW DOORS |
| | MENTIONED (NEW LED FILLED SLIDING AND SWING DOOR / NEW |
| | 3'-0 X 7'-0 METAL DOOR ARE INSTALLED AT PRESENT AND |
| | WILL BE REPLACED WITH THE DOOR BUT THE FRAME IS |
| | EXISTING. IF THESE ARE COMPLETE NEW DOORS THEY SHALL |
| | MEET THE REQUIREMENTS OF FBC 1714.5. UNLESS OTHER WISE |
| | TESTED, BUCKS SHALL EXTEND BEYOND THE INTERIOR FACE OF |
| | THE WINDOW OR DOOR FRAME SUCH THAT FULL SUPPORT OF THE |
| | FRAME IN PROVIDED.106.1.2* ADDITIONAL INFORMATION IS |
| | REQUIRED TO CLEARLY SHOW THE INTENT OF THE REMODEL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THE CODE. 106.1.1. WHAT IS THE SIZE OF |
| | THE CONCRETE PADS FOR THE NEW CONDENSING UNITS? SHOW |
| | THE DETAIL INFORMATION FOR THE SLABS ON THE DRAWINGS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |