2008-06-27 09:04:23BUILDING PLAN REVIEW
 PERMIT: 08060598
 ADD: 580 VILLAGE BLVD. #315
 CONT: RYBEK CONSTRUCTION INC.
 TEL: (561)798-5122
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-27-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)THE OCCUPANCY TYPE INDICATED ON THE PLANS IS
 BUSINESS/ ORDINARY HAZARD. THE OF TYPES OF HAZARDOUS
 GROUPS MENTION IN THE FBC 2004 SECTION 306 ARE F-1
 MODERATE-HAZARD/ F-2 LOW-HAZARD AND F-3 WHICH IS A
 SPECIAL PURPOSE FACTORY INDUSTRIAL OCCUPANCY. THEN
 THERE IS THE HIGH HAZARD IN SECTION 307. ONE OF THE
 ABOVE MENTION GROUPS SHALL BE CHOSEN INSTEAD OF
 ORDINARY HAZARD. IF THIS IS BUSINESS ONLY, REMOVE THE
 ORDINARY HAZARD FROM THE DRAWINGS.
  
 4)FBC 106.3.5.1.1(5) FIRE SPRINKLER PLANS REQUIRED TO
 SHOW THE LAYOUT OF THE SPRINKLER HEADS IN RELATION THE
 RENOVATION. THE LAYOUT OF THE SPRINKLER HEADS MAY BE
 SHOWN ON THE REFLECTED CEILING PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER