| Plan Review Notes For Permit 08060582 |
| Permit Number |
08060582 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-11-06 11:02:38 | | | | | | | | | | | | | | | | PROVISO | | | | | | 250.32(B)(2) GROUNDED CONDUCTOR WHERE (1) AN EQUIPMENT | | | GROUNDING CONDUCTOR IS NOT RUN WITH THE SUPPLY TO THE | | | BUILDING OR STRUCTURE, (2) THERE ARE NO CONTINUOUS | | | METALLIC PATHS BONDED TO THE GROUNDING SYSTEM IN EACH | | | BUILDING OR STRUCTURE INVOLVED, AND (3) GROUND-FAULT | | | PROTECTION OF EQUIPMENT HAS NOT BEEN INSTALLED ON THE | | | SUPPLY SIDE OF THE FEEDER(S), THE GROUNDED CONDUCTOR | | | RUN WITH THE SUPPLY TO THE BUILDING OR STRUCTURE SHALL | | | BE CONNECTED TO THE BUILDING OR STRUCTURE DISCONNECTING | | | MEANS AND TO THE GROUNDING ELECTRODE(S) AND SHALL BE | | | USED FOR GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES, | | | OR FRAMES REQUIRED TO BE GROUNDED OR BONDED.---IF THESE | | | CONDITIONS ARE NOT MET, AN EQUIPMENT GROUND MUST BE | | | INSTALLED WITH THE FEEDERS, AND THE NEUTRAL ISOLATED | | | INTHE EXISTING MAIN SWITCHGEAR. | | 2008-11-04 15:16:25 | | | | | | | |
|