| Plan Review Notes For Permit 08060582 |
| Permit Number |
08060582 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-14 13:35:14 | ***FAILED*** | | | | | | 1) THE DRIVE AISLE ADJACENT TO THE GENERATOR WILL NEED | | | TO BECOME ONE-WAY, AS IT WILL ONLY BE 15 FEET IN WIDTH. | | | I SUGGEST THAT A "DO NOT ENTER" SIGN BE INSTALLED IN | | | THE LANDSCAPE ISLAND TO PREVENT PEOPLE FROM DRIVING | | | SOUTH THROUGH THE AISLE (SEE ATTACHED SKETCH FOR | | | LOCATION OF SIGN). | | | | | | 2) AS NOTED PREVIOUSLY, ALL MECHANICAL EQUIPMENT WILL | | | NEED TO BE SCREENED PURSUANT TO SECTION 94-444(B) OF | | | THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS | | | (ZLDRS): | | | | | | A) THE PROPOSED PVC FENCE SHALL COMPLETELY ENCLOSE THE | | | GENERATOR. | | | B) THE FENCE SHALL BE LANDSCAPE WITH SHRUBS/HEDGES | | | PLANTED AT 2 FOOT INTERVALS. | | | C) THE SHRUBS/HEDGES SHALL BE PROTECTED FROM VEHICULAR | | | ENCROACHMENT BY MEANS OF CURBING. | | | D) THE SWITCHGEAR AND TRANSFORMER SHALL ALSO BE | | | PROPERLY SCREENED. | | | | | | QUESTIONS/COMMENTS CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. | | 2008-07-09 17:34:05 | PLANNING AND ZONING: | | | | | | CURRENTLY PENDING MINOR AMENDMENT REVIEW FROM THE | | | PLANNING AND ZONING DEPT. | | | | | | ANY QUESTIONS, PLEASE CONTACT JOHN ROACH AT 822-1448. |
|