| Plan Review Notes For Permit 08060582 |
| Permit Number |
08060582 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-17 14:04:23 | *** PROVISO *** | | | 1) FUEL STORAGE TANK MUST BE A MINIMUM OF 5 FEET FROM | | | THE BUILDING, PER NFPA 30 4.3.2.1.1. | | | 2) THE GENERATOR MUST BE A MINIMUM OF 5 FEET FROM ANY | | | BUILDING OPENINGS, PER NFPA 37 4.1.4. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|