| 2008-06-23 08:39:17 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | NOTE: SUBMITTED DRAWING IS NOT INDICATING |
| | CORROSPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. PER-2004 FBC FUEL |
| | GAS SECTION 401.1 SCOPE. |
| | NOTE: SUBMITTED DRAWING DOES NOT INDICATE ANY PIPING |
| | MATERIALS BEING INSTALLED. |
| | |
| | 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| | BEING USED ON THE DRAWINGS. PER FBC-2004 FUEL GAS |
| | SECTION 401.1 SCOPE. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: REFERENCE COMMENT #1. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: A PERMIT INFORMATION SEARCH OF SAID ADDRESS DOES |
| | NOT INDICATE AN APPROVED POOL PERMIT WITH A POOL |
| | HEATER. PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS |
| | FOR THE PROPOSED POOL HEATER CLEARLY INDICATING THE |
| | MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| | FROM A NATIONALLY RECOGNIZED TESTING LAORATORY. |
| | |
| | 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | 7. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. |
| | THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE |
| | TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES |
| | MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL |
| | CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS, |
| | ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND |
| | PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR |
| | PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES |
| | (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT |
| | APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION |
| | 108.3 BUILDING PERMIT VALUATION. |
| | PER MARSHALL AND SWIFT A 400,000 BTU HEATER IS AROUND |
| | $3000.00. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |