| Date |
Text |
| 2008-11-21 16:26:06 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- SHEET C1: |
| | A) SETBACKS SHOWN ON SITE PLAN DON'T MATCH SETBACKS |
| | SHOWN ON SURVEY. REVISE AS REQUIRED. |
| | |
| | B) FOOTPRINT OF NEW ADDITIONS SHOWN ON SITE PLAN DON'T |
| | MATCH FOOTPRINT AND DIMENSIONS SHOWN ON FLOOR PLAN AND |
| | AND FOUNDATION PLAN. REVISE AS REQUIRED. SEE COMMENTS |
| | ON SHEET C1. |
| | |
| | C) TYPE OF CONSTRUCTION (3B) SPECIFIED ON CODE |
| | INFORMATION IS FOR 2 HOUR FIRE CONCRETE BLOCK |
| | CONSTRUCTION. CLARIFY IF REALLY BUILDING A 2 HOUR FIRE |
| | RATED CONSTRUCTION OR SPECIFY CORRECT BUILDING TYPE. |
| | TYPE 3B CONSTRUCTION REQUIRES MANUFACTURER |
| | SPECIFICATIONS FOR TWO HOUR FIRE RATED CONCRETE BLOCK. |
| | |
| | D) CODE INFORMATION SPECIFIES 10 PSF LIVE LOAD AT |
| | BOTTOM OF ROOF TRUSS CHORD. THIS MEANS THAT ATTIC IS |
| | NOT DESIGNED FOR STORAGE. CLARIFY IF DESIGNING SPACE |
| | FOR ATTIC STORAGE OR NOT SINCE SIZE OF ATTIC ACCESS |
| | PANEL OF 22"X48" SHOWN ON ATTIC AREA ABOVE NEW MASTER |
| | BEDROOM SUGGESTS ATTIC ACCESS BIG ENOUGH TO ALLOW FOR |
| | STORAGE. CLEARLY SPECIFY ON PLANS IF ATTIC IS DESIGNED |
| | FOR STORAGE OR NOT. IF SO SPECIFY CORRECT ATTIC LIVE |
| | LOAD. SEE TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 2- SHEET A1: |
| | A) SPECIFY SAFETY GLASS FOR WINDOW BY THE TUB IN NEW |
| | MASTER BATHROOM AS REQUIRED BY SEC. R308.4 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) WALL LEGEND DOESN'T SPECIFY TYPE OF CONSTRUCTION FOR |
| | NEW 4" AND 6" INTERIOR WALLS. SPECIFY CONSTRUCTION TYPE |
| | (EG: WOOD OR METAL STUDS) AND PROVIDE COMPLETE |
| | SPECIFICATIONS TO VERIFY COMPLIANCE WITH CHAPTER 6 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 3- SHEET A3: |
| | A) REVISE WALL SECTION A/A-3. FOOTING NEEDS TO BE MIN. |
| | 12" BELOW GRADE. ACCORDING TO FOUNDATION PLAN FOOTING |
| | IS 16" HIGH. IF TOP OF FOOTING IS 6" ABOVE GRADE, THEN |
| | THERE IS ONLY 10" BELOW GRADE. REVISE AS REQUIRED. SEC. |
| | R403.1.4 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) SPECIFY TRUSS CONNECTORS TO EXISTING NORTH WALL IN |
| | NEW MASTER BEDROOM AREA. NONE SPECIFIED ON THIS AREA. |
| | |
| | 4- SHEET A4: |
| | A) CLARIFY SIZE OF STRUCTURAL BUCK DETAIL FOR WINDOW |
| | HEAD DETAIL, WINDOW SILL DETAIL AND WINDOW JAMB DETAIL. |
| | WINDOW JAMB DETAILS CALLS FOR 2X AND 1X BUCK. REVISE AS |
| | REQUIRED. |
| | |
| | B) PROVIDE STRUCTURAL BUCK DETAIL FOR EXTERIOR DOOR. |
| | SEE PRODUCT APPROVAL FOR MINIMUM SIZE REQUIRED. |
| | |
| | 5- NOTICE OF COMMENCEMENT: |
| | A) IS EXPIRED AFTER 30 DAYS OF BEING RECORDED IF WORK |
| | IS NOT STARTED. NEED TO HAVE NEW RE-RECORDED ONE. |
| | ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT |
| | PICK UP TO AVOID EXPIRATION. |
| | |
| | B) NOTICE OF COMMENCEMENT NEEDS TO COMPLETE INFORMATION |
| | FOR DESCRIPTION OF IMPROVEMENT. INFORMATION WAS LEFT |
| | BLANK. |
| | |
| | 6- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD (561)233-5120) TO VERIFY IF |
| | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY |
| | OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 7- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) GLASS BLOCK AS SHOWN ON PLANS. |
| | |
| | B) ARCHED WINDOWS AS SHOWN ON PLANS. |
| | |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 9- PROVIDE SPECIFICATIONS FOR ROOF SHEATHING INCLUDING |
| | NAIL TYPE AND SPACING AS REQUIRED BY SEC. R803.2.3.1 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: TAKE INTO CONSIDERATION ROOF ZONE 3. SEE CITED |
| | SECTION ABOVE FOR NAILING IN ROOF ZONE 3. |
| | |
| | 10- GARAGE AREA WAS CONVERTED TO LIVING AREA. SPECIFY |
| | HOW WALLS ARE GETTING THE REQUIRED INSULATION. PROVIDE |
| | WALL SECTION/SPECIFICATIONS TO VERIFY COMPLIANCE WITH |
| | CHAPTER 13 FBC 2004. |
| | |
| | 11- OWES $731.38 FOR UPDATED PERMIT VALUATION AND RADON |
| | FEES. |
| | |
| | 12- ENERGY CALCULATIONS: |
| | A) COMPLETE INFORMATION ON TOP OF FORM. |
| | |
| | B) REVISE ITEM #10. CEILING TYPE IS UNDER ATTIC, NOT |
| | SINGLE ASSEMBLY. REVISE AS REQUIRED. |
| | |
| | C) REVISE INFORMATION ON SECOND PAGE. CALCULATIONS ARE |
| | NO DONE FOR WORST CASE SCENARIO. THEREFORE, OPENINGS |
| | NEED TO BE SHOWN ON THE ACTUAL CARDINAL ORIENTATION. |
| | SEE PLANS AND SURVEY FOR CORRECT CARDINAL ORIENTATION |
| | AND NUMBER OF WINDOWS. COORDINATE INFORMATION WITH |
| | ADDITIONS SHOWN ON PLANS. |
| | |
| | D) REVISE PAGE TWO: OVERHANG LENGTH AND OVERHANG HEIGHT |
| | ARE INCORRECT. NEED TO MATCH INFORMATION SHOWN ON |
| | PLANS. ALSO, SEE ITEM #11C ABOVE. |
| | |
| | 13- HURRICANE SHUTTERS: |
| | A) PROVIDE COMPLETE INSTALLATION SCHEDULE AS REQUIRED |
| | BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS |
| | IMPACT PROTECTION. . SEE ATTACHED COPY. |
| | |
| | B) ENGINEER OF RECORD FOR THIS PROJECT IS LUIS A LOPEZ. |
| | CLARIFY WHY THIS PRODUCT APPROVAL NOA 06-0110.04 WAS |
| | REVIEWED AND APPROVED BY ANOTHER ENGINEER (JOHN HOLT). |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |