| 2008-06-23 08:57:08 | ***FAILED*** |
| | |
| | |
| | 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH |
| | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. |
| | |
| | 2)THE REAR ADDITION AS SHOWN DOES NOT MEET THE REAR |
| | SETBACK REQUIREMENT...PREVIOUS COMMENTS WERE BASED ON |
| | SUBMITTED INFORMATION, INFORMATION HAS CHANGED. |
| | PURSUANT TO SECTION 94-75 OF THE CITY'S ZONING AND LAND |
| | DEVELOPMENT REGULATIONS:MINIMUM REAR SETBACK = 15' OR |
| | 10% OF THE LOT DEPTH, WHICHEVER IS LESS.AS THE LOT |
| | DEPTH IS NOW SHOWN AS 75', THE MINIMUM REAR SETBACK IS |
| | 7.5'...SURVEY TO CONFIRM. |
| | |
| | 3)PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED |
| | OFF-STREET PARKING SPACES FOR LESS THAN FOUR |
| | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE |
| | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED |
| | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE |
| | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT |
| | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN |
| | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, |
| | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION |
| | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO |
| | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. |
| | |
| | |
| | PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE |
| | SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE |
| | FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT |
| | BUILDING FACADE). |
| | |
| | 4)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C |
| | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION |
| | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT |
| | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. |
| | |
| | 5)CLARIFY "CHANGING THE LOOK OF THE FRONT FACADE" AS |
| | INDICATED BY THE PERMIT APPLICATION.WHAT IMPROVEMENTS |
| | ARE BEING DONE?NOTE:AS THE EXISTING FRONT FACADE IS |
| | NONCONFORMING WITH RESPECT TO ITS FRONT SETBACK |
| | DIMENSION, NO IMPROVEMENT SHALL BE MADE WHICH INCREASES |
| | THIS NONCONFORMITY.PLEASE CLARIFY. |
| | |
| | 6)THE SOUTH ELEVATION AS SHOWN ON SHEET A-2 CALLS |
| | OUT A "NEW ENTRY", OTHER ELEVATIONS SHOW "EXISTING |
| | ENTRY".PLEASE CLARIFY.NOTE:AS THE EXISTING FRONT |
| | FACADE IS NONCONFORMING WITH RESPECT TO ITS FRONT |
| | SETBACK DIMENSION, NO IMPROVEMENT SHALL BE MADE WHICH |
| | INCREASES THIS NONCONFORMITY. |
| | |
| | |
| | |
| | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, |
| | ZONING TECHNICIAN (561)805-6720 |
| | [email protected] |
| | |
| | |
| | |
| | |