Plan Review Notes
Plan Review Notes For Permit 08060578
Permit Number 08060578
Review Stop M
Sequence Number 1
Notes
Date Text
2008-06-24 16:21:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) PLEASE SUBMIT THE COMPLETE COOLING LOAD
 CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1. THE COOLING
 LOAD CALCULATIONS THAT WERE SUBMITTED CONSIST OF, THREE
 COPIES OF THE SAME PAGE.
  
 3) PLEASE SHOW THE CLOTHES DRYER VENT ON THE MECHANICAL
 PLAN, PER 2004 FBC/R M1501.1.
  
 4) THE COOLING LOAD CALCULATIONS ARE CALLING FOR 38,577
 TOTAL COOLING BTU'S, THE MECHANICAL PLAN EQUIPMENT
 SCHEDULE IS SHOWING 47,200 TOTAL COOLING BTU'S, THE
 PLANS CAN ONLY CALL FOR 15% MORE TOTAL COOLING BTU'S
 THAN THE COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1.1. PLEASE CORRECT. SEE ATTACHED ARI
 CERTIFICATE SHOWING A 3.5 TON SYSTEM THAT WOULD MEET
 THE REQUIREMENTS.
  
 5) PLEASE ROTATE THE HOUSE ON THE MECHANICAL PLAN SO IT
 IS FACING THE SAME AS THE OTHER BUILDING PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]