| 2008-06-24 16:21:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 2) PLEASE SUBMIT THE COMPLETE COOLING LOAD | | | CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1. THE COOLING | | | LOAD CALCULATIONS THAT WERE SUBMITTED CONSIST OF, THREE | | | COPIES OF THE SAME PAGE. | | | | | | 3) PLEASE SHOW THE CLOTHES DRYER VENT ON THE MECHANICAL | | | PLAN, PER 2004 FBC/R M1501.1. | | | | | | 4) THE COOLING LOAD CALCULATIONS ARE CALLING FOR 38,577 | | | TOTAL COOLING BTU'S, THE MECHANICAL PLAN EQUIPMENT | | | SCHEDULE IS SHOWING 47,200 TOTAL COOLING BTU'S, THE | | | PLANS CAN ONLY CALL FOR 15% MORE TOTAL COOLING BTU'S | | | THAN THE COOLING LOAD CALCULATIONS, PER 2004 FBC | | | 13-607.1.ABC.1.1. PLEASE CORRECT. SEE ATTACHED ARI | | | CERTIFICATE SHOWING A 3.5 TON SYSTEM THAT WOULD MEET | | | THE REQUIREMENTS. | | | | | | 5) PLEASE ROTATE THE HOUSE ON THE MECHANICAL PLAN SO IT | | | IS FACING THE SAME AS THE OTHER BUILDING PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|