Notes
Date Text
2008-06-24 10:09:37 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A2, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} A DISCONNECT PER 230.70(A)(1) MUST BE ADDED TO THE
 SERVICE AND DRAWN ON THE RISERDUE TO THE RELOCATION OF
 THE ELECTRICAL PANEL.
  
 2} THERE IS A NOTE REGARDING THE REWIRE OF THE
 RESIDENCE ON THE FLOOR PLAN, AND THERE ARE NOTES IN THE
 BEDROOMS, LIVING AND DINING ROOMS INDICATING EXISTING
 OUTLETS TO REMAIN., PLEASE CLARIFY THE SCOPE OF WORK.
  
 3} IN THE NEW DINING ROOM THE RECEPTACLES MUST COMPLY
 WITH 210.52(B)(1).
  
 4}PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.
  
 5} SHEET M-1 FLOOR PLAN DOES NOT CORRELATE WITH ANY
 OTHER SHEETS SUBMITTED. SHOW THE LOCATION OF THE A/C
 EQUIPMENT ON THEELECTRICAL PLAN. ALSO SHOW COMPLIANCE
 WITH THE REQUIRED DISCONNECT PER 440.14,RECEPTACLE
 PER 210.63
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718