| Plan Review Notes For Permit 08060578 |
| Permit Number |
08060578 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-24 10:09:37 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET A2, UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1} A DISCONNECT PER 230.70(A)(1) MUST BE ADDED TO THE | | | SERVICE AND DRAWN ON THE RISERDUE TO THE RELOCATION OF | | | THE ELECTRICAL PANEL. | | | | | | 2} THERE IS A NOTE REGARDING THE REWIRE OF THE | | | RESIDENCE ON THE FLOOR PLAN, AND THERE ARE NOTES IN THE | | | BEDROOMS, LIVING AND DINING ROOMS INDICATING EXISTING | | | OUTLETS TO REMAIN., PLEASE CLARIFY THE SCOPE OF WORK. | | | | | | 3} IN THE NEW DINING ROOM THE RECEPTACLES MUST COMPLY | | | WITH 210.52(B)(1). | | | | | | 4}PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, | | | 106.3.5.4 FBC AS AMENDED. | | | | | | 5} SHEET M-1 FLOOR PLAN DOES NOT CORRELATE WITH ANY | | | OTHER SHEETS SUBMITTED. SHOW THE LOCATION OF THE A/C | | | EQUIPMENT ON THEELECTRICAL PLAN. ALSO SHOW COMPLIANCE | | | WITH THE REQUIRED DISCONNECT PER 440.14,RECEPTACLE | | | PER 210.63 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|