| 2008-07-04 09:35:21 | DENIED |
| | |
| | 1) PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 & |
| | 2007AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2) IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 4) THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $731.76 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | |
| | 5) PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE |
| | PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR |
| | SETBACKS, NOTE THAT SURVEY AND SITE PLAN MEASUREMENTS |
| | DO NOT MATCH |
| | |
| | 6) PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. |
| | |
| | 7) SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR TO SUBMITTAL. NOTE: WHOLE HOUSE |
| | METHOD A WAS CHOSEN PLEASE CORRECT THE AS-BUILT |
| | CALCULATIONS FOR THE GLAZED OPENINGS TO REFLECT ACTUAL |
| | CONDITIONS ON THE DRAWINGS, AMOUNT OF OPENINGS, |
| | ORIENTATION, OVERHANG LENGTH AND HEIGHT, ETC. |
| | |
| | 8) PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER |
| | R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES |
| | |
| | 9) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 10) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 11) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN |
| | BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG. WHEN |
| | AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE |
| | DENIED |
| | |
| | 12) NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF |
| | SHINGLES, GLASS BLOCK, MULLIONS FOR JOINED WINDOWS, |
| | FIXED WINDOWS IN FAMILY ROOM, AND LINTELS. PLEASE NOTE |
| | THAT GLASS BLOCK USING A MORTAR SYSTEM ONLY MEETS SMALL |
| | MISSILE IMPACT (FL # 1363), THE SILICONE METHOD WILL |
| | MEET LARGE MISSILE RATING (FL # 5357) |
| | |
| | 13) IF WOOD BUCKS ARE TO BE USED AN ATTACHMENT DETAIL |
| | IS REQUIRED FOR THE TRANSFER OF APPLICABLE LOADS TO THE |
| | BUILDING PER R613.6.1.1 FBC RES. |
| | SEE DOOR PRODUCT APPROVALS |
| | |
| | 14) SUBMIT 2 COPIES OF THE SIGNED AND SEALED ENGINEERED |
| | TRUSS DRAWINGS THAT COMPLY WITH R802.10.1 FBC WITH |
| | PERMIT APPLICATION OR BEFORE INSTALLATION THAT HAVE |
| | BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 15) BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT |
| | |
| | 16) IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE |
| | OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2 |
| | ORIGINAL COPIES OF A SOIL TEST REPORT SHALL BE |
| | SUBMITTED PER R401.4 FBC RES. |
| | |
| | 17) PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| | REQUIRED PER R807.1 FBC RES. |
| | |
| | 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, |
| | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. |
| | IF THESE FEES HAVE BEEN PAID PLEASE HAVE NO FEE STAMP |
| | ON NEW SETS OF DRAWINGS |
| | |
| | 19) PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN |
| | THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING, |
| | THE NOTICE IS VOID. PLEASE NOTE THAT NO IMPROVEMENT WAS |
| | GIVEN IN THE OLD NOC THIS AREA MUST BE FILLED OUT IN |
| | THE NEW ONE. IN ORDER TO AVOID THE 90 DAY RULE NOC CAN |
| | BE RECORDED ONCE THE PERMIT HAS BEEN ISSUED. |
| | |
| | 20) PRODUCT APPROVALS WERE SUBMITTED FOR FLAT ROOF |
| | PRODUCT BUT NO FLAT ROOF ON THE PLANS, ALSO FOR AN |
| | INSWING FIBERGLASS DOOR WITH SIDELITES THAT IS NOT |
| | PRESENT ON DRAWINGS, PLEASE CLARIFY |
| | |
| | 21) PLEASE CLARIFY NEW WORK TO FRONT FACADE OF HOUSE, |
| | SHEET A2, SOUTH ELEVATION SHOWS NEW ENTRY AND A1 STATES |
| | EXISTING IS THE NEW SCOPE OF WORK FOR THE FRONT ONLY |
| | NEW WINDOWS? |
| | |
| | 22) REMOVE ALL OLD PAGES, NON USED PRODUCT APPROVALS, |
| | ETC. FROM PACKAGE AND RESUBMIT 2 COMPLETE SETS WITH |
| | REVISIONS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY FOR |
| | REFERENCE. |
| | |
| | 23) ADDITIONAL PERMITS WILL BE REQUIRED FOR MECHANICAL |
| | AND DRIVEWAY |
| | |