Plan Review Notes
Plan Review Notes For Permit 08060566
Permit Number 08060566
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-24 13:05:33 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} 210.12(B) DWELLING UNIT BEDROOMS ALL 120-VOLT,
 SINGLE PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS
 SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
 INTERRUPTER, COMBINATION TYPE INSTALLED TO PROVIDE
 PROTECTION OF THE BRANCH CIRCUIT. A NOTE ON THE PLAN
 WILL SUFFICE.
  
 3} THERE ARE RECEPTACLES SHOWN IN THE LIVING AND DINING
 ROOMS THAT APPEAR TO BE FLOOR RECEPTACLES. CLARIFY IF
 THESE ARE FLOOR OR WALL. IF FLOOR AN ENGINEERING REPORT
 WILL BE REQUIRED TO VERIFY THE STRUCTURAL INTEGRITY OF
 ANY CUTS IN THE FLOOR.
  
 4} SUBMIT A FIXTURE SCHEDULE INDICATING THE TYPE AND
 WATTAGES FOR THE NEW FIXTURES.106.1.1 FBC.
  
 NOTE PER 304.1SCOPE.
 LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. THE
 EXTENSION OF THE ELECTRICAL SYSTEM CONSTITUTED A LEVEL
 2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718