| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| | 106.1.3.FBC. |
| | |
| | 2} 210.12(B) DWELLING UNIT BEDROOMS ALL 120-VOLT, |
| | SINGLE PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS |
| | SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS |
| | SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT |
| | INTERRUPTER, COMBINATION TYPE INSTALLED TO PROVIDE |
| | PROTECTION OF THE BRANCH CIRCUIT. A NOTE ON THE PLAN |
| | WILL SUFFICE. |
| | |
| | 3} THERE ARE RECEPTACLES SHOWN IN THE LIVING AND DINING |
| | ROOMS THAT APPEAR TO BE FLOOR RECEPTACLES. CLARIFY IF |
| | THESE ARE FLOOR OR WALL. IF FLOOR AN ENGINEERING REPORT |
| | WILL BE REQUIRED TO VERIFY THE STRUCTURAL INTEGRITY OF |
| | ANY CUTS IN THE FLOOR. |
| | |
| | 4} SUBMIT A FIXTURE SCHEDULE INDICATING THE TYPE AND |
| | WATTAGES FOR THE NEW FIXTURES.106.1.1 FBC. |
| | |
| | NOTE PER 304.1SCOPE. |
| | LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF |
| | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR |
| | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, |
| | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. THE |
| | EXTENSION OF THE ELECTRICAL SYSTEM CONSTITUTED A LEVEL |
| | 2. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |