| Plan Review Notes For Permit 08060556 |
| Permit Number |
08060556 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-19 16:16:31 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.SEE SHEET 8, A 2.5 INCH EDGE DISTANCE REQUIRES A | | | .75 FACTOR APPLIED TO ANCHOR SPACING. | | | | | | 2.INSTALLATION SCHEDULE SPECIFIES 9" AND 8.5; THE | | | CHART WHICH YOU HAVE CIRCLED SHOWS 9" AND 6.5, BUT BOTH | | | NUMBERS NEED TO HAVE .75 FACTOR APPLIED.PLEASE REVISE | | | INSTALLATION SCHEDULE. |
|