| Plan Review Notes For Permit 08060552 |
| Permit Number |
08060552 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-10-02 11:56:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | | | | 1. ONE SET OF THE ELEVATION PLAN WHICH SPECIFIES DESIGN | | | PRESSURES WAS A PHOTOCOPY. DOCUMENTS PREPARED BY AN | | | ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS. FS481. | | | | | | 2. THE ARCHITECT HAS SPECIFIED DESIGN PRESSURE OF | | | -47.34, BUT ANCHORING FOR 47.2 HAS BEEN USED. PLEASE | | | REVISE; A DESIGN PRESSURE OF -47.34 EXCEEDS 47.2 AND | | | THEREFORE THE ANCHORING FOR -77PSF SHOULD BE USED. | | | | | | 3. THE INSTALLATION SCHEDULE STAES THAT THE SUBSTRATE | | | IS "CEMENT". THIS SHOULD STATE EITHER "CONCRETE" OR | | | "BLOCK". IF THIS IS BLOCK, PLEASE USE THE CHART ON PAGE | | | 8 OF THE ACCORDION PRODUCT APPROVAL. | | | | | | |
|