Plan Review Notes
Plan Review Notes For Permit 08060552
Permit Number 08060552
Review Stop B
Sequence Number 2
Notes
Date Text
2008-10-02 11:56:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. ONE SET OF THE ELEVATION PLAN WHICH SPECIFIES DESIGN
 PRESSURES WAS A PHOTOCOPY. DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. FS481.
  
 2. THE ARCHITECT HAS SPECIFIED DESIGN PRESSURE OF
 -47.34, BUT ANCHORING FOR 47.2 HAS BEEN USED. PLEASE
 REVISE; A DESIGN PRESSURE OF -47.34 EXCEEDS 47.2 AND
 THEREFORE THE ANCHORING FOR -77PSF SHOULD BE USED.
  
 3. THE INSTALLATION SCHEDULE STAES THAT THE SUBSTRATE
 IS "CEMENT". THIS SHOULD STATE EITHER "CONCRETE" OR
 "BLOCK". IF THIS IS BLOCK, PLEASE USE THE CHART ON PAGE
 8 OF THE ACCORDION PRODUCT APPROVAL.
  
  