2008-07-01 11:06:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.ONE PHOTOCOPY OF THE WIND LOAD CHART
 (ENGINEERING EXPRESS) WAS SUBMITTED.HOWEVER, IT IS
 NOT CLEAR WHY THIS WAS SUBMITTED AS THE ARCHITECT
 SPECIFIED WIND LOADS.ENGINEERING IS NOT REQUIRED FOR
 BUILDINGS UNDER 60' AS THE BUILDING CODE SPECIFIES WIND
 PRESSURES.PLEASE EITHER REMOVE THE WIND LOAD CHARTS
 (ENGINEERING EXPRESS) OR PROVIDE ANOTHER ORIGINAL.
  
 2.TWO COMPLETE ORIGINAL COLLATED SETS OF PERMIT
 DOCUMENTS REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS
 SUBMITTED, AND ONE SET OF ENGINEERING WAS A PHOTOCOPY
 (SEE ITEM1).DUE TO WORKLOAD, I AM UNABLE TO MAKE
 PHOTOCOPIES FOR CONTRACTORS.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.THIS WAS NOT SUBMITTED FOR THE ROLL UP
 SHUTTERS.
  
 4.THE SPAN SHOULD BE ONE NUMBER, NOT TWO.FOR
 ACCORDIONS THIS WILL CORRELATE WITH THE BLADE LENGTH.
 FOR ROLL UP SHUTTERS, IT WILL BE THE HORIZONTAL
 DIMENSION.
  
 5.THE SHUTTER CONNECTION MOUNTING TYPE SHOULD
 CORRELATE WITH THE ANCHOR CHART ON THE PRODUCT
 APPROVAL.FOR THE ACCORDIONS, YOU'VE MARKED C2.
 PLEASE REVISE THE INSTALLATION SCHEDULE.