| 2008-07-01 11:06:02 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471.ONE PHOTOCOPY OF THE WIND LOAD CHART |
| | (ENGINEERING EXPRESS) WAS SUBMITTED.HOWEVER, IT IS |
| | NOT CLEAR WHY THIS WAS SUBMITTED AS THE ARCHITECT |
| | SPECIFIED WIND LOADS.ENGINEERING IS NOT REQUIRED FOR |
| | BUILDINGS UNDER 60' AS THE BUILDING CODE SPECIFIES WIND |
| | PRESSURES.PLEASE EITHER REMOVE THE WIND LOAD CHARTS |
| | (ENGINEERING EXPRESS) OR PROVIDE ANOTHER ORIGINAL. |
| | |
| | 2.TWO COMPLETE ORIGINAL COLLATED SETS OF PERMIT |
| | DOCUMENTS REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS |
| | SUBMITTED, AND ONE SET OF ENGINEERING WAS A PHOTOCOPY |
| | (SEE ITEM1).DUE TO WORKLOAD, I AM UNABLE TO MAKE |
| | PHOTOCOPIES FOR CONTRACTORS. |
| | |
| | 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72.THIS WAS NOT SUBMITTED FOR THE ROLL UP |
| | SHUTTERS. |
| | |
| | 4.THE SPAN SHOULD BE ONE NUMBER, NOT TWO.FOR |
| | ACCORDIONS THIS WILL CORRELATE WITH THE BLADE LENGTH. |
| | FOR ROLL UP SHUTTERS, IT WILL BE THE HORIZONTAL |
| | DIMENSION. |
| | |
| | 5.THE SHUTTER CONNECTION MOUNTING TYPE SHOULD |
| | CORRELATE WITH THE ANCHOR CHART ON THE PRODUCT |
| | APPROVAL.FOR THE ACCORDIONS, YOU'VE MARKED C2. |
| | PLEASE REVISE THE INSTALLATION SCHEDULE. |