2008-07-09 10:29:22** DENIEDREVIEW **
  
 1) NOTE: PLEASE ADJUST PLANS AND CORRELATE ALL
 ELECTRICAL ITEMS ON THE ELECTRICAL RISER WITH THE
 EQUIPMENT SCHEDULE, CONDUCTOR SCHEDULE AND PANEL
 SCHEDULE WITH LOADS.
 SOME EXAMPLES OF THESE ITEMS WILL BE LISTED AS A
 BENEFIT AND MAY NOT BE ALL ITEMS WHICH DO NOT
 CORRELATE.
  
 FOR EXAMPLE:
 EQUIPMENT #10 ON THE LEGEND INDICATES A POOL/SPA LIGHT
 YET PLEASE SEE THE RISER WHICH SHOWS ONE OF THE PUMPS
 WITH THIS SAME NUMBER 10.
  
 FOR EXAMPLE:
 PLEASE SEE THE CIRCLE #3 WHICH IS LISTED ON LEGEND AS A
 PUMP YET THE RISER DO NOT INDICATE THIS SAME #3. IN
 FACT SOME PUMPS LISTED ARE NOT SHOWN.
  
 2) NOTE: PLEASE INDICATE THE SIZE OF THE FEEDERS AND
 AMPACITY OF THE FEED TO THE NEW POOL EQUIPMENT PANEL
 SHOWN. AS PERMIT FOR BASE BUILDING HAS NOT BEEN ISSUED
 INCLUSIVE OF INTERIOR BUILD OUT WORK THERE ARE NO
 RECORD PLANS WHICH SHOW THESE ITEMS.
 220, 408, 215.5, 310.16 ETC
 FBC 106.1.1 FOR CLARITY AND ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE SHOW THE COMPLETE GROUNDING SYSTEM FOR
 THE EQUALPOTENTIAL BONDING. THE COVER SHEET SHOWS A
 LINE AND MENTIONS *GROUND PER CODE* HOWEVER YOU MAY NOT
 QUOTE THE CODE OR PARTS OF THE CODE IN LIEU OF ACTUAL
 DESIGN.
 680.26
 NEC 2005,
 FBC 106.1.1, 106.1.2, 106.5 FOR ADDITIONAL INFORMATION,
 CLARITY AND INFORMATION ON RECORD PLANS.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  