| Plan Review Notes For Permit 08060529 |
| Permit Number |
08060529 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-19 13:13:32 | 1. THE TEMPORARY STANDPIPE SHALL BE INSTALLED IN A | | | METHOD THAT ALLOWS FOR ITS USE. THE TEMPORARY STANDPIPE | | | SHALL BE PROPERLY SUPPORTED TO PREVENT MOVEMENT. IF | | | USED BY THE FIRE RESCUE DEPARTMENT IT CAN BE EXPECTED | | | THAT 150 PSIG WILL BE INTRODUCED INTO THE SYSTEM. | | | | | | 2. THE TEMPORARY STANDPIPE SHALL BE KEPT UP WITH | | | CONSTRUCTION ACTIVITIES. | | | | | | 3. THE TEMPORARY STANDPIPE SHALL REMAIN IN PLACE AND | | | FULLY FUNCTIONAL UNTIL THE PERMANENT STANDPIPES ARE | | | INSTALLED AND APPROVED FOR USE. | | | | | | 4. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE | | | VISIBLE AND ACCESSIBLE TO RESPONDING EMERGENCY SERVICES | | | PERSONNEL. | | | | | | 5. A TEMPORARY SIGN SHALL BE PROVIDED TO ASSIST | | | EMERGENCY RESPONDERS IN LOCATING THE TEMPORARY | | | STANDPIPE SYSTEM LOCATION. | | | | | | 6. HOSE VALVES SHALL BE KEPT CLOSED AND BE PROTECTED | | | FROM DAMAGE. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|