Plan Review Notes
Plan Review Notes For Permit 08060529
Permit Number 08060529
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-06-19 13:13:321. THE TEMPORARY STANDPIPE SHALL BE INSTALLED IN A
 METHOD THAT ALLOWS FOR ITS USE. THE TEMPORARY STANDPIPE
 SHALL BE PROPERLY SUPPORTED TO PREVENT MOVEMENT. IF
 USED BY THE FIRE RESCUE DEPARTMENT IT CAN BE EXPECTED
 THAT 150 PSIG WILL BE INTRODUCED INTO THE SYSTEM.
  
 2. THE TEMPORARY STANDPIPE SHALL BE KEPT UP WITH
 CONSTRUCTION ACTIVITIES.
  
 3. THE TEMPORARY STANDPIPE SHALL REMAIN IN PLACE AND
 FULLY FUNCTIONAL UNTIL THE PERMANENT STANDPIPES ARE
 INSTALLED AND APPROVED FOR USE.
  
 4. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE
 VISIBLE AND ACCESSIBLE TO RESPONDING EMERGENCY SERVICES
 PERSONNEL.
  
 5. A TEMPORARY SIGN SHALL BE PROVIDED TO ASSIST
 EMERGENCY RESPONDERS IN LOCATING THE TEMPORARY
 STANDPIPE SYSTEM LOCATION.
  
 6. HOSE VALVES SHALL BE KEPT CLOSED AND BE PROTECTED
 FROM DAMAGE.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX