| 2009-12-01 16:43:39 | BUILDING PLAN REVIEW |
| | PERMIT: 08060519 |
| | ADD: 309 CLEMATIS ST |
| | CONT: WELLINGTON EQUESTRIAN |
| | TEL: (561)951-6729 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISIONS DATED: |
| | ARCHITECTURAL: REVISION# 4 NOV. 4/2009 |
| | STRUCTURAL: REVISION# 3 NOV.2/ 2009 |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | 1) SHEET A-1 THE FRONT ENTRY STAIRWAY REVISION# 2 HAS |
| | NOT BEEN UPDATED, THE REVISION SUBMITTED DOES INDICATE |
| | THE STEEL COLUMN IN THE STAIRWELL BUT THE EGRESS |
| | CALCULATIONS FOR BOTH THE STAIRS AND FRONT ENTRY |
| | INDICATE THE PERMIT SET OF EGRESS CALCULATIONS, NOT |
| | WHAT IS CURRENTLY BUILT. PLEASE REVISE PLANS INDICATING |
| | THE REVISED SSTAIR AND DOORWAY EGRESS CALCULATION FOR |
| | THE FRONT STAIR AND ENTRY. PLEASE INCLUDE THE UPDATED 1 |
| | HR RATED WALL ASSEMBLY WITH THE VERTICAL STEEL BEAMS |
| | LOCATED |
| | OUTSIDE OF THE 1 HOUR RATED ASSEMBLY. 1020.1.2 |
| | PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN |
| | EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | PLEASE NOTE THE FIRST FLOOR ENTRY DOOR IS NOT LOCATED |
| | ON THE DOOR SCHEDULE LOCATED ON SHEET A-15. |
| | |
| | 2) SHEET A-2 THE FRONT ROOFTOP STAIRWAY LOCATED IN THE |
| | BOTTOM RIGHT CORNER OF THE SHEET INDICATES A NEW 3'-0" |
| | DOOR THAT LEADS INTO THE MECHANICAL ROOM LOCATED |
| | BENEATH THE THIRD FLOOR LEVEL. PLEASE REVIEW SECTIONS : |
| | VERTICAL EXIT ENCLOSURES |
| | 1020.1.1 OPENINGS AND PENETRATIONS. EXIT ENCLOSURE |
| | OPENING PROTECTIVE???S SHALL BE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF SECTION 715. |
| | |
| | EXCEPT AS PERMITTED IN SECTION 402.4.6, OPENINGS IN |
| | EXIT ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR |
| | OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| | ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES |
| | AND FOR EGRESS FROM THE ENCLOSURE. |
| | |
| | 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS |
| | THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR |
| | REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY |
| | FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTION 712. THERE SHALL BE NO PENETRATIONS OR |
| | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| | BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | 3A) SHEET A-3 INDICATES A NEW DUMBWAITER, NOT NOTED ON |
| | THIS SHEET BUT S-2, S-3 AND S-29 INDICATE AS SUCH. |
| | PLEASE PROVIDE THE WALL TYPES TO BE ASSOCIATED WITH THE |
| | SHAFT CONSTRUCTION A-3 DOES PROVIDE SHAFT AND WALL |
| | TYPES BUT NO WALL SECTION TAG IS PROVIDED FOR THE |
| | BUMBWAITER.. 3002.1 HOISTWAY ENCLOSURE PROTECTION. |
| | ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES |
| | SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 707. |
| | 3002.1.1 OPENING PROTECTIVES. OPENINGS IN HOISTWAY |
| | ENCLOSURES SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7. |
| | |
| | 3B) SHEET S-29 THE DUMBWAITER INDICATES HOW THE |
| | STRUCTURAL MEMBERS WILL BE INSTALLLED ON THE FIRST AND |
| | SECOND FLOOR BUT NO INFORMATION IS PROVIDED PAST THE |
| | SECOND FLOOR ROOF LINE. ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 3C) 3004.1 VENTS REQUIRED. HOISTWAYS OF ELEVATORS AND |
| | DUMBWAITERS PENETRATING MORE THAN THREE STORIES SHALL |
| | BE PROVIDED WITH A MEANS FOR VENTING SMOKE AND HOT |
| | GASES TO THE OUTER AIR IN CASE OF FIRE. |
| | |
| | 3D) PLEASE ALSO REVIEW SECTION 3006 FOR ELEVATOR |
| | MACHINE ROOMS SECTION 1-6. |
| | |
| | 3E) A-3 THE ORIGINAL ISSUED PLANS DOES INDICATE A THIRD |
| | FLOOR KITCHEN THE NEW REVISION INDICATES THE REMOVAL OF |
| | THE KITCHEN AND ADDITIONAL DINING AREA, PLEASE UPDATE |
| | THE OCCUPANCY LOADS FOR THE THIRD FLOOR AND EGRESS OF |
| | THE STAIRS, IF THIS FLOOR CONTAINS THE HIGHEST |
| | CONCENTRATION OF OCCUPANTS. TABLE 1004.1.1& TABLE |
| | 1005.1. |
| | |
| | 4) SHEET A-5 WEST ELEVATION THE OPENING PROTECTIVES, |
| | FIRE SHUTTERS ARE STILL INDICATED ON PLANS, THERE HAS |
| | BEEN RECENT DISCUSSION WITH THE CONTRACTOR, DESIGNER |
| | AND OWNER ABOUT THE ELIMINATION OF THE FIRE SHUTTERS |
| | AND THE USE OF A HINGED COLLASPABLE WALL SECTION THAT |
| | WAS SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW UNDER |
| | ALTERNATE MATERIALS AND METHODS, TO DATE NO FORMAL |
| | SUBMITTAL HAS BEEN BROUGHT IN TO THE CITY FOR REVIEW. |
| | 104.11 ALTERNATE MATERIALS, DESIGN OF METHODSOF |
| | CONSTRUCTION AND EQUIPMENT. |
| | |
| | 5) SHEET A-8.1 INDICATES CABANAS TO BE DETERMINED BY |
| | OWNER, A SEPERATE PERMIT REVIEW AND ASSOCIATED FEES |
| | WILL BE REQUIRED. NOTE WIND INFORMATION OF HOW CABANAS |
| | WILL MEET WIND LOADING: WIND DESIGN SEECTION 1609. |
| | |
| | JIM WITMER C. B. O. |