| 2009-11-20 07:41:20 | REVISIONS |
| | |
| | 1. ROOF ACCESS DOOR TO INTERSTITIAL SPACE IS NOT |
| | ALLOWED WHICH IS SHOWN ON PAGE A-2.0. THIS OPENING IS |
| | TO BE SEALED WITH THE PROPER FIRE RATING OF THE EXIT |
| | ENCLOSURE FOR WHICH IT IS LOCATED. |
| | |
| | 2. A NEW FIRE DEPARTMENT CONENCTION WAS TO HAVE BEEN |
| | INSTALLED ON THE SOUTH SIDE OF THE BUILDING TO REPLACE |
| | THE EXISTING SNOOT. THE NEW DOUBLE FIRE DEPARTMENT |
| | CONNECTION IS TO BE LOCATED WITHIN 150 FEET OF A FIRE |
| | HYDRANT. THE PLAN SEEM TO SUUEST THAT THE FIRE |
| | DEPARTMENT CONNECTION WILL BE PLACED ON THE RISER WHICH |
| | WOULD BE LOCATED ON THE NORTH SIDE OF THE BUILDING. |
| | PLEASE COORDINATE THE PLACEMENT OF THE NEW FIRE |
| | DEPARTMENT CONNECTION. KNOX-LOCKING CAPS ARE REQUIRED |
| | FOR THE NEW FIRE DEPARTMENT CONNECTION. THE EXISTING |
| | SNOOT NEEDS TO BE REMOVED. |
| | |
| | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW KITCHEN |
| | HOODS, DUCTS, AND FIRE SUPPRESSION SYSTEMS. |
| | |
| | 4. ON PAGE E-12 IT APPEARS THAT FIRE ALARM EQUIPMENT |
| | WILL BE CONNECTED TO THE EXISTING FIRE ALARM CONTROL |
| | PANEL. ON PAGE E-11 HORN STROBES ARE SHOWN IN THE FIRE |
| | ALARM LEGEND. DUE TO THE OCCUPANT LOAD OF THE BUILDING |
| | SPEAKER STROBES WITH A VOICE EVACUATION MESSAGE WILL BE |
| | REQUIRED. A FIRE ALARM PERMIT IS REQUIRED FOR THE FIRE |
| | ALARM WORK PLANNED FOR THE THIRD FLOOR. THE ENTIRE |
| | BUILDING SHALL BE EQUIPPED WITH SPEAKER STROBE DEVICES. |
| | |
| | 5. THE FIRE SPRINKLER DRAWINGS MAY NOT BE ILLUSTRATIVE |
| | TO THE WORK THAT HAS BEEN PERFORMED IN THE FIELD. |
| | PLEASE COORDINATE DRAWINGS WITH THE WORK AND CORRECT |
| | DISCREPANCIES. |
| | |
| | |
| | DENIED |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |