| Plan Review Notes For Permit 08060519 |
| Permit Number |
08060519 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-05 15:07:43 | REVIEW FOR THIS SCOPE OF WORK PERFORMED UNDER PROJECT | | | PERMIT #08070215 | | | | | | NOTE: EXTENSION AND RELOCATION OF EXISTING KITCHEN | | | EXHAUST SHALL BE UNDER SEPARATE PERMIT AND EXCLUDED | | | FROM THIS SCOPE OF WORK. | | | | | | NOTE FOR YOUR INFORMATION: MECHANICAL PLAN SHOWS THE | | | KITCHEN EXHAUST FAN AT A MINIMUM HEIGHT OF 40" ABOVE | | | THE ROOD SURFACE. ARCHITECTURAL PLANS SHOW THE FAN | | | SURROUNDED ON 3 SIDES BY A 42" HIGH PARAPET. IF FAN IS | | | TO BE LOCATED IN CLOSE PROXIMITY TO PARAPET (MIN. 2' | | | SEPARATION) THE DISCHARGE OPENING OF THE FAN MUST BE | | | HIGHER THAN THE PARAPET IN ACCORDANCE WITH FBC-M | | | 506.5.5. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|