| 2009-09-23 16:10:45 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | REVIEW DONE AT THE REQUEST OF THE BUILDING OFFICIAL FOR |
| | THE PREVIOUS REVIEWER: |
| | |
| | A. SHT P-1 SUBMITTED FOR REVISION DOES NOT INDICATE A |
| | REVISION NUMBER NOR DOES IT INDICATE WHERE THE REVISION |
| | IS LOCATED BECAUSE OF THE LACK OF REVISION CLOUDS. THAT |
| | SAID, THE SANITARY PIPING HAS BEEN DELETED, MANY |
| | FIXTURES HAVE BEEN DELETED FROM THE PLUMBING FIXTURE |
| | SCHEDULE SUCH AS THE W/C'S, LAVS, FAUCETS, URINAL, |
| | FLOOR SINKS, HOSE BIBB & WATER HEATER. PLEASE CLARIFY, |
| | HAVE THESE FIXTURES BEEN CHANGED, DELETED OR BOTH? |
| | SECTIONS 106.1.1, 106.2 & 106.1.3. |
| | |
| | B. SHT P-2 HAS COMPLETLY DIFFERENT INFORMATION THAN |
| | WHAT IS ON FILE FOR PUBLIC RECORD. WILL ALL THE |
| | INFORMATION FOR THE BARS BE DELETED? PLEASE CLARIFY. |
| | SECTIONS 106.1.1, 106.2 & 106.1.3. |
| | |
| | *****FROM PREVIOUS REVIEW PERMIT NUMBER 09020194**** |
| | |
| | A. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED: |
| | |
| | 1. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A LISTED SHUT |
| | OFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH |
| | MP REGULATOR. SECTION 409.4. A UNION IS REQUIRED |
| | DOWNSTREAM OF THE SHUT OFF VALVE NEAR THE REGULATOR FOR |
| | SERVICING & REPLACEMENT. |
| | |
| | 2. SHT P-2 GAS DISTRIBUTION ISOMETRIC. INDICATE THE |
| | TOTAL BTU'S FOR THE EXISTING KITCHEN & DISTANCE TO THE |
| | MOST REMOTE OUTLET IN THE KITCHEN ON THE RISER DIAGRAM. |
| | SECTION 106.1.2 MORE INFORMATION REQUIRED AND SECTION |
| | 402 PIPE SIZING. |
| | |
| | 4. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES |
| | GAS PIPE SIZE PER TABLE 402.4(20) P.E. PIPE. PLEASE |
| | INDICATE WHERE THE P.E. PIPE WILL BE INSTALLED. (P.E. |
| | FOR OUTDOOR UNDERGROUND ONLY). SECTION 404.14.1. |
| | |
| | 5. SHT P-2 GAS DISTRIBUTION ISOMETRIC. PLEASE INDICATE |
| | GAS TYPE. (IF LP GAS MORE COMMENTS WILL BE |
| | FORTHCOMING). |
| | |
| | 6. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A MANUAL SHUT |
| | OFF VALVE IS REQUIRED UPSTREAM OF THE EMERGENCY HOOD |
| | SHUT DOWN SHUT OFF VALVE. |
| | |
| | 7. SHT P-2 GAS DISTRIBUTION ISOMETRIC. SUBMIT MANUF. |
| | SPECIFICATION SHEETS FOR THE UNIONS. INDICATE MODEL |
| | NUMBER AND SHOW BTU CAPACITY FOR TOTAL LOAD OF ALL |
| | APPLIANCES COMBINED. SECTION 410.2(1)(2)(3). |
| | |
| | 8. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES |
| | GAS PIPE SIZE PER TABLE 402.4(2) WHICH IS .5 PSI OR |
| | LESS, BUT DELIVERY PRESSURE IS INDICATED AT 5 PSI. |
| | PLEASE CLAIRFY. SECTION 402. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |