| 2008-07-16 14:35:10 | BUILDING PLAN REVIEW |
| | PERMIT: 08060519 |
| | ADD: 309 CLEMATIS ST |
| | CONT: PLAN REVIEW CON JOHN WEBB |
| | TEL: (561)312-6247 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. 2 COPIES OF |
| | RESPONCE COMMENTS WERE SUBMITTED AND COMMENTS 1 & 2 |
| | WERE ONLY RESPONDED TOO. |
| | |
| | 1B) COMPLIED, 3 SETS OF DOCUMENTS SUBMITTED, THRESHOLD |
| | BUILDING BECAUSE OF OCCUPANT LOAD. |
| | |
| | 1C)INFORMATIONAL |
| | |
| | 1D )FL S S 713.13NOTICE OF COMMENCEMENT, TO BE |
| | FILED WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF |
| | THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) 2ND REQUEST,PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.NOTE |
| | THIS IS AN ADDITION AND THE 2004 EXISTING BUILDING CODE |
| | CHAPTER 9 WILL NEED TO BE ADDRESSED. SHEET DT-1 |
| | INDICATES A LEVEL II ALTERATION, THIS MAY BE TRUE FOR |
| | THE INTERIOR WORK UNDER ANOTHER PERMIT. THIS WORK IS TO |
| | BE COVERED UNDER 2004 EXISTING BUILDING CODE CHAPTER 9 |
| | ADDITIONS, PLEASE MAKE CORRECTIONS. |
| | |
| | 1F-H) COMPLIED. |
| | |
| | 2) 2ND REQUEST, THE DESIGNER OF RECORD HAS NOT PROVIDED |
| | WHAT THE BASE DESIGN IS FOR WIND IN SHEETS A-1- A-4. |
| | PLANS ARE MISSING THE WIND DESIGN CRITERIA. 1603.1.4 |
| | WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO |
| | WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND |
| | LOADS GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING |
| | SYSTEM OF THE BUILDING: |
| | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. |
| | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | 5.COMPONENTS AND CLADDING. THE DESIGN WIND |
| | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE |
| | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS |
| | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 3) 2ND REQUEST,THIS BUILDING IS CLASSIFIED AS A |
| | THRESHOLD BUILDING BECAUSE THE OCCUPANT LOAD IS GREATER |
| | THAN 500 OCUPANTS. |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 3A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. CONTACT KEN CONRADMANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 3C) COMPLIED. |
| | |
| | 4)SOILS REPORTS COMPLIED. |
| | |
| | 5) 2ND REQUEST, THE PLANS INDICATE TWO DIFFERENT |
| | ENGINEERS IT APPEARS THAT ONE WILL BE A SPECIALTY |
| | ENGINEER AND THE OTHER THE ENGINEER OF RECORD FOR THE |
| | PROJECT, OR TO TAKE RESPONSIBILITY FOR THE PROJECT. THE |
| | DESIGNER OF RECORD WILL NEED TO REVIEW ALL SHOP |
| | DRAWINGS AND APPLY THEIR SHOP DRAWING STAMP ONCE PLANS |
| | ARE REVIEWED AND APPROVED.FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |