| 2008-10-03 10:54:49 | RESIDENTIAL (R2) SHUTTERS, BUILDING REVISION CHECKLIST. |
| | REVIEW UNDER 2004 FBC . |
| | |
| | 1- BUILDING REVISION CALLS FOR SHUTTER PROTECTION ON |
| | WINDOWS. THIS TYPE OF BUILDING REQUIRES SHUTTERS |
| | INSTALLATION APPROVAL PLAN TO BE APPROVED BY THE |
| | BUILDING OFFICIAL. FOR PUBLIC SAFETY REASONS INDICATE |
| | HOW ARE REMOVABLE SHUTTERS GOING TO BE INSTALLED ON THE |
| | WINDOWS OF THIS MULTISTORY BUILDING BY THE APARTMENT |
| | OWNER IN THE EVENT OF A HURRICANE. |
| | |
| | 2- DESIGN PRESSURES INDICATED IN THE CITY OF WEST PALM |
| | BEACH INSTALLATION SCHEDULE ARE ASSUMING THAT BUILDING |
| | IS DESIGNED AS ENCLOSED BUILDING. FURTHER RESEARCH |
| | NEEDS TO BE DONE. FOR SOME REASON OPENINGS HAVE NOT |
| | IMPACT GLAZING AND THERE ARE NOT EXISTING SHUTTERS. |
| | BUILDING CAN'T BE DESIGNED AS ENCLOSED IF THE OPENINGS |
| | ARE NOT PROTECTED. THEREFORE, NEED TO USE THE PARTIALLY |
| | ENCLOSED BUILDING DESIGN PRESSURES. |
| | ***NOTE: THIS ISSUE WILL BE BROUGHT TO THE BUILDING |
| | OFFICIAL ATTENTION FOR FURTHER DISCUSSION. |
| | |
| | 2- FLORIDA PRODUCT APPROVAL FL8363-R1 SUBMITTED IS FOR |
| | 2007 CODE VERSION. CURRENT CODE VERSION IS 2004. NEED |
| | TO PROVIDE PRODUCT APPROVAL FOR CURRENT CODE VERSION. |
| | |
| | 3- INSTALLATION NOTES ON FLORIDA PRODUCT APPROVAL |
| | FL8363-R1 (2007 CODE VERSION) STATES THAT DEFLECTION |
| | NOT REQUIRED OUTSIDE HVHZ. AS MENTIONED ON PREVIOUS |
| | COMMENT THIS PRODUCT APPROVAL ONLY APPLIES TO 2007 CODE |
| | VERSION. THERE IS ANOTHER PRODUCT APPROVAL FOR 2004 |
| | CODE VERSION WHICH DOESN'T HAVE THIS PROVISION. |
| | THEREFORE MUST FOLLOW DEFLECTION REQUIREMENTS. |
| | |
| | 4- INSTALLATION SCHEDULE AND ANCHOR SCHEDULE |
| | HIGHLIGHTED ON PAGE 15 INDICATE THAT THE SUBSTRATE TO |
| | RECEIVE THE SHUTTERS IS 3000 PSI CONCRETE. SHUTTERS ARE |
| | GOING TO BE INSTALLED HORIZONTALLY. BUILDING HAS |
| | CONCRETE BLOCK WALLS, NOT CONCRETE. NEED TO REVISE |
| | INSTALLATION SCHEDULE ANCHOR SPACING USING THE CONCRETE |
| | BLOCK TABLES, EVEN IS THERE ARE CONCRETE BLOCK FILLED |
| | CELLS. OTHERWISE, PROVIDE COMPLETE TESTING SHOWING THAT |
| | FILLED CELLS ARE 3000PSI MIN. |
| | |
| | 5- PERMIT VALUATION WAS UPDATED TO REFLECT THE |
| | ADDITIONAL SHUTTERS. THEREFORE OWES $15.48 FOR UPDATED |
| | VALUATION. |
| | |
| | 6- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS |
| | REQUIRED BY SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 7- ENGINEER DESIGN PRESSURES CALCULATIONS HAVE A COPY |
| | OF HIS SIGNATURE INSTEAD OF HIS ORIGINAL SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND SEC. |
| | 61G15-23.002 OF ENGINEER'S FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |