| 2008-07-01 16:56:17 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 2- SHEET 1 OF 2:CLEARLY SPECIFY THE ATTIC LIVE LOAD |
| | AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | NOTE: THIS LOAD IS IN ADDITION TO THE BOTTOM CHORD DEAD |
| | LOAD. |
| | |
| | 3- WINDOWS SPECIFIED FOR THE NEW BEDROOM DON'T COMPLY |
| | WITH THE EGRESS REQUIREMENTS OF SEC. R311.1.2 OF 2004 |
| | FLORIDA RESIDENTIAL CODE.SH-48X52 WINDOWS DON'T |
| | PROVIDE THE MINIMUM HEIGHT CLEARANCE.ALSO, CLARIFY IF |
| | WINDOW WILL BE A CUSTOM MADE WINDOW. SEE PRODUCT |
| | APPROVAL FOR STANDARD WINDOW SIZES.PROVIDE |
| | MANUFACTURER'S CUT SHEETS FOR WINDOWS OTHER THAN THE |
| | STANDARD EGRESS WINDOWS TO VERIFY COMPLIANCE WITH SEC. |
| | R310.1.2. |
| | |
| | 4- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED |
| | BY DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS. COPIES OF PRODUCT APPROVAL |
| | SUBMITTED ARE MISSING THE TOP PART OFTHE DRAWINGS. |
| | PROVIDE COPIES WITH COMPLETE INFORMATION. |
| | |
| | B) SWING DOOR AT NEW CLOSET AREA. |
| | |
| | C) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS.PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN TO SAVE |
| | TIME AND PAPER. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- SHEET 2 OF 2: |
| | A) REVISE ROOF SHEATHING NAIL SPACING FOR ZONE #3. |
| | SEE SEC. R803.2.3.1 FOR REQUIRED NAIL SPACING AT ROOF |
| | ZONE #3 AND REVISEROOF SHEATHING NAILING SCHEDULE AS |
| | REQUIRED. |
| | |
| | B) SPECIFY THE MINIMUM THICKNESSMOISTURE BARRIER |
| | AT CONCRETE SLAB AS REQUIRED BY SEC. R406.3.2. |
| | |
| | 6- OWES $3.80 FOR RADON FEES. |
| | |
| | 7- ENGINEER TO DATE PLANS WHEN THEY ARE SIGNED AND |
| | SEALED AS REQUIRED BY SEC. 61G15-23.002 FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |