| 2008-12-18 17:05:46 | BUILDING REVIEW APPROVED WITH PROVISO: (NOTE: PROVIDE |
| | INFORMATION PRIOR TO CONSTRUCTION OR INSTALLATION TO |
| | AVOID CONFLICTS OR DELAYS) |
| | |
| | 1- REVISE ENERGY CALCULATIONS. REVISE TOTAL UNDER ATTIC |
| | SQUARE FOOTAGE SHOWN ON ITEM #10A TO COMPLY WITH THE |
| | REQUIREMENTS OF CEILING AREA SEC. 13-604.1.A.1 FBC |
| | 2004. |
| | NOTE: DON'T FORGET TO HAVE ALL SIGNATURES AND DATES AT |
| | BOTTOM OF FORM 600A-2004R. |
| | |
| | 2- SPECIFY HOW LONG ARE THE ANCHORS SPECIFIED ON |
| | DOOR/WINDOW STRUCTURAL BUCK DETAILS. HOW MUCH EMBEDMENT |
| | IS REQUIRED INTO THE SUBSTRATE. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH |
| | SECTIONS R301 AND R613.6 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 3- DESIGN CRITERIA NEEDS TO SPECIFY ALL DESIGN LOADS |
| | INCLUDING THE ATTIC LIVE LOAD FOR STORAGE OR |
| | NON-STORAGE AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 4- SHEET 3: |
| | A) TYPICAL WALL SECTION: SPECIFY FIREBLOCKING AS |
| | REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) REVISE STUCCO FINISH ON SOFFIT TO COMPLY WITH TABLE |
| | R702.1(1) OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) SPECIFY FOOTING SIZE BELOW GRADE TO VERIFY |
| | COMPLIANCE WITH SEC. R403.1.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | D) SIZE OF WINDOW SPECIFIED FOR BEDROOM #3 (24SH) |
| | DOESN'T COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. |
| | R310.1.2 OF 2004 FLORIDA RESIDENTIAL CODE. REVISE AS |
| | REQUIRED. |
| | |
| | E) GARAGE DOOR LEADING TO THE INSIDE OF THE HOUSE NEEDS |
| | TO COMPLY WITH THE REQUIREMENTS OF SEC. R309.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED. |
| | |
| | 5- SHEET 4: |
| | A) PROVIDE COMPLETE ROOF FRAMING PLAN INCLUDING THE |
| | AREAS THAT DON'T HAVE ROOF TRUSSES BUT CONVENTIONAL |
| | FRAMING BY BUILDER. SPECIFY ALL CONNECTORS. |
| | |
| | B) REVISE TRUSS ANCHOR SCHEDULE. FOR SOME CONNECTOR THE |
| | MAX. ACTUAL UPLIFT EXCEEDS THE ALLOWABLE UPLIFT. REVISE |
| | AS REQUIRED. ALSO, COORDINATE WITH PRODUCT APPROVAL FOR |
| | CURRENT UPLIFT LOADS AND REVISE AS REQUIRED. |
| | |
| | 6- SHEET 5: |
| | A) SPECIFY DIMENSIONS FOR ROOF ZONES: SEE FIGURE |
| | R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE FOR MINIMUM |
| | DIMENSIONS AND REVISE AS REQUIRED. |
| | |
| | B) SPECIFY HOW PROVIDING THE ATTIC VENTILATION IN |
| | COVERED ENTRY ROOF DETAIL TO VERIFY COMPLIANCE WITH |
| | SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) REVISE THICKNESS OF STUCCO FINISH ON COVERED ENTRY |
| | DETAIL. SEE ITEM 3B ABOVE. |
| | |
| | 7- SURVEY NEEDS TO HAVE ORIGINAL SIGNATURE AS REQUIRED |
| | BY SEC. 61G17-7.0025 OF FLORIDA ADMINISTRATIVE CODE AND |
| | CHAPTER 472 FLORIDA STATUTE. |
| | |
| | 8- RE-SUBMIT PRODUCT APPROVAL FOR FRENCH DOORS. NOA |
| | 05-1116.06 EXPIRED ON JUNE 05, 2008. |