| 2008-06-23 14:51:14 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 3, PROPOSED FLOOR PLAN: PLEASE CLARIFY IF A |
| | NEW DBL SINK W/DISP & DW IS BEING INSTALLED OR IF THE |
| | EXISTING ARE BEING REUSED. PER FBC- PLUMBING SECTION |
| | 401.1 SCOPE. |
| | |
| | 2. SHEET 7,SANITARY RISER AT MASTER BATH: THE RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET 3. |
| | CLEARLY IDENTIFY ALL PROPOSED FIXTURES ON THE RISER |
| | DIAGRAM. IT APPEARS THAT THERE ARE 2 WATER/CLOSETS |
| | BEING INDICATED INSTEAD OF ONE. PER FBC- PLUMBING |
| | SECTION 401.1 SCOPE. |
| | |
| | 3. SHEET 7, SANITARY RISER AT BATH #3 & UTILITY: THE |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET |
| | 3. THE WASHING MACHINE IS BEING INDICATED IN THE WRONG |
| | LOCATION AND THE LAUNDRY TUB IS NOT BEING INDICATED AT |
| | ALL. PER FBC- PLUMBING SECTION 701.1 SCOPE. |
| | NOTE: THE WASHING MACHINE MUST DRAIN DOWNSTREAM OF THE |
| | WET VENTED BATHROOM GROUP. PER FBC- PLUMBING SECTION |
| | 909.1 WET VENT PERMITTED. |
| | |
| | 4. SHEET 7, ON BOTH THE MASTER BATH AND BATH #3 |
| | SANITARY RISER DIAGRAMS: CLEARLY INDICATE THE CLEANOUT |
| | AT THE JUCTION OF THE BUILDING DRAIN AND BUILDING SEWER |
| | AS BEING A TWO-WAY CLEANOUT. PER FBC- PLUMBING SECTION |
| | 708.3.5. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |