2008-06-23 14:51:14PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 3, PROPOSED FLOOR PLAN: PLEASE CLARIFY IF A
 NEW DBL SINK W/DISP & DW IS BEING INSTALLED OR IF THE
 EXISTING ARE BEING REUSED. PER FBC- PLUMBING SECTION
 401.1 SCOPE.
  
 2. SHEET 7,SANITARY RISER AT MASTER BATH: THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET 3.
 CLEARLY IDENTIFY ALL PROPOSED FIXTURES ON THE RISER
 DIAGRAM. IT APPEARS THAT THERE ARE 2 WATER/CLOSETS
 BEING INDICATED INSTEAD OF ONE. PER FBC- PLUMBING
 SECTION 401.1 SCOPE.
  
 3. SHEET 7, SANITARY RISER AT BATH #3 & UTILITY: THE
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET
 3. THE WASHING MACHINE IS BEING INDICATED IN THE WRONG
 LOCATION AND THE LAUNDRY TUB IS NOT BEING INDICATED AT
 ALL. PER FBC- PLUMBING SECTION 701.1 SCOPE.
 NOTE: THE WASHING MACHINE MUST DRAIN DOWNSTREAM OF THE
 WET VENTED BATHROOM GROUP. PER FBC- PLUMBING SECTION
 909.1 WET VENT PERMITTED.
  
 4. SHEET 7, ON BOTH THE MASTER BATH AND BATH #3
 SANITARY RISER DIAGRAMS: CLEARLY INDICATE THE CLEANOUT
 AT THE JUCTION OF THE BUILDING DRAIN AND BUILDING SEWER
 AS BEING A TWO-WAY CLEANOUT. PER FBC- PLUMBING SECTION
 708.3.5.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  