2008-06-18 09:49:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) NEED TO SHOW THE SUPPLY AND RETURN AIR GRILL SIZES
 AND CFM'S ON THE MECHANICAL PLAN, PER 2004 WPB AMEND.
 106.3.5.4 (10).
  
 3) THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN IS
 SHOWING THE WRONG MODEL NUMBER AND HEATER KW FOR AIR
 HANDLER UNIT #1 (SEE RED LINE INFORMATION ON MECHANICAL
 PLAN), PLEASE CORRECT PER 2004 WPB AMEND.106.3.5.4
 (10).
  
 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]