| 2008-06-17 13:33:02 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, |
| | 106.3.5.4 FBC AS AMENDED.THERE ARE THREE SMALL |
| | APPLIANCE CIRCUITS ON ONE CIRCUIT, NO BATH CIRCUIT IS |
| | SHOWN (210.11(C)(3), THE CONDENSING UNITS ARE NOT SHOW, |
| | ETC. |
| | |
| | 3} PLEASE SUBMIT A SITE PLAN INDICATING THE LOCATION OF |
| | THE METER AND THE MAIN DISCONNECT. |
| | |
| | 4} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| | FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH |
| | 250.66 ALL AVAILABLE. ALSO SEE 250.52(A)(3) FOR FOOTER |
| | STEEL. |
| | |
| | 6} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE SAME ON |
| | THE PLANS. |
| | |
| | 7} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| | AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING. |
| | |
| | 8} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NECLOCATE ON THE PLANS TO SHOW |
| | COMPLIANCE IN ALL ROOMS |
| | |
| | 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |