2008-08-05 08:37:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-17-08 NOTE #5. THE AIR
 HANDLER MODEL NUMBERS TWE0400E13FB LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE AND THE CONDENSER UNIT MODEL NUMBER
 2TTX5024A1000A STATUS HAS BEEN DISCONTINUED, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;