| 2008-06-23 13:26:21 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1 FLOOR PLAN: CLEARLY IDENTIFY ALL PROPOSED |
| | PLUMBING FIXTURES ON THE FLOOR PLAN. SHEET MEP-1 |
| | SANITARY RISER DIAGRAM IS INDICATING A SHOWER, HOWEVER |
| | ON SHEET A-1 FLOOR PLAN THIS FIXTURE APPEARS TO BE A |
| | TUB. PLEASE CLARIFY AND CORRELATE SHEETS. PER FBC- |
| | PLUMBING SECTION 401.1 SCOPE. |
| | |
| | 2. SHEET MEP-1 SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN ON SHEET A-1 PER THE FOLLOWING. |
| | |
| | A} ONE LAVATORY IS MISSING FROM THE RISER DIAGRAM. |
| | |
| | B} THE WASHING MACHINE IS MISSING FROM THE RISER |
| | DIAGRAM. |
| | |
| | PLEASE CLEARLY INDICATE ALL PROPOSED FIXTURES ON THE |
| | RESUBMITTED SANITARY RISER DIAGRAM. PER FBC- PLUMBING |
| | SECTION 701.1 SCOPE. PLEASE CLEARLY INDICATE THE |
| | FOLLOWING FOR THE WASHING MACHINE. |
| | |
| | C} 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | D} 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | |
| | E} 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | 3". |
| | |
| | F} 708.9 ACCESS. ACCESS SHALL BE |
| | NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | LOCATED AT 4' A.F.F. |
| | PROVIDED TO ALL CLEANOUTS. |
| | |
| | G} PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | NOTE: THE WASHING MACHINE SHALL DISCHARGE DOWNSTREAM |
| | OF THE PROPOSED WET VENTED BATHROOM GROUP. |
| | |
| | 3. SHEET MEP-1 SANITARY RISER DIAGRAM: THE SHOWER |
| | REQUIRES A WATER-SEAL TRAP AND THE WATER CLOSET DOES |
| | NOT REQUIRE A WATER-SEAL TRAP DUE TO HAVING AN INTEGRAL |
| | TRAP. PER FBC- PLUMBING SECTION 1002.1 FIXTURE TRAPS. |
| | |
| | 4. SHEET MEP-1 SANITARY RISER DIAGRAM: CLEARLY SIZE |
| | THE LAVATORY TRAP. PER (W.P.B. AS AMENDED) SECTION |
| | 106.3.5.4 (9) PLUMBING. |
| | |
| | 5. SHEET MEP-1 PLUMBING NOTES #11: AIR CHAMBERS ARE |
| | NOT APPROVED UNLESS INSTALLED PER "STANDARD PDI-WH-201, |
| | A RECHARGEABLE TYPE OF AIR CHAMBER" IS INSTALLED AND A |
| | DETAIL OF THIS TYPE OF AIR CHAMBER IS REQUIRED TO BE ON |
| | THE PLANS OR DELETE AIR CHAMBER FROM THE PLANS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |