2008-06-17 15:04:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER ALSO, PER 2004 FBC 13-103.1.1,
  
 2) THE ENERGY CALCULATIONS LINE 15 IS TAKING THE
 CEILING FAN CREDIT. THE PLANS SHOW NO CEILING FAN IN
 THE NEW GUEST BEDROOM SO THIS CREDIT CAN NOT BE TAKEN,
 PER 2004 FBC 13-607.2.A.3.1.
  
 3) ENERGY CALCULATIONS LINE 10A SHOWS R-30 FOR CEILING
 INSULATION, PLAN A-2 IS SHOWING R-19 FOR CEILING
 INSULATION. PLEASE CORRECT PLANS PER 2004 FBC
 13-103.3.
  
 4) THE COOLING LOAD CALCULATIONS ARE CALLING FOR 14,545
 TOTAL COOLING BTU'S, THE MECHANICAL PLAN EQUIPMENT
 SCHEDULE IS SHOWING 27,000 TOTAL COOLING BTU'S, THE
 PLANS CAN ONLY CALL FOR 15% MORE TOTAL COOLING BTU'S
 THAN THE COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1.1. A NOTE ON PLAN MEP-1 STATES 'SMALLEST
 AVAILABLE PRODUCT LINE ETC.' SEE ATTACHED ARI PRINT-OUT
 SHOWING TRANE MAKES 83 SYSTEMS THAT MEET THE
 REQUIREMENTS OF THE COOLING LOAD CAL'S AND ENERGY
 CAL'S. PLEASE CORRECT.
  
 5)THE AIR HANDLER MODEL NUMBERS TWE0400E13FB LISTED
 ON THE A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE
 ARI DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]