Plan Review Notes
Plan Review Notes For Permit 08060438
Permit Number 08060438
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-17 11:19:26 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE NEW GUEST BEDROOM NEEDS A RECEPTACLE TO COMPLY
 WITH 210.52(A)(1).
  
 2} LOCATE PANEL "B" ON THE PLAN. 106.1.3 FBC AS
 AMENDED.
  
 3} THE BATH CIRCUIT FOR THE NEW MASTER BATH MUST COMPLY
 WITH 210.11(C)(3). THE PANEL SCHEDULE PROVIDED FOR
 PANEL "B" DOES NOT INCLUDE THAT CIRCUIT. IT IS UNCLEAR
 IF THAT CIRCUIT IS SUPPLIED FROM THE EXISTING PANEL.
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE THE
 SMOKE ALARMS ON THE PLAN AND NOTE THE INTERCONNECTION
 REQUIREMENT WITH THE EXISTING ALARMS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718