2008-07-14 16:33:102004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SURVEY/SITE PLAN INDICATING THE DISTANCE TO
 PROPERTY LINES AND ADJACENT STRUCTURES. IF DISTANCES TO
 PROPERTY LINES ARE LESS THAN 6 FEET,SPECIFY THE
 DISTANCE TO STRUCTURES ON THE ADJACENT PARCELS. SEE FBC
 R302.1 EXTERIOR WALLS. EXTERIOR WALLS SEPARATED BY LESS
 THAN 6 FEET (1828 MM) SHALL HAVE NOT LESS THAN A
 ONE-HOUR FIRE-RESISTIVE RATING WITH EXPOSURE FROM BOTH
 SIDES. PROJECTIONS SHALL NOT EXTEND TO A POINT CLOSER
 THAN 4 FEET (1220 MM) FROM AN ADJACENT PROJECTION OR
 WALL.
  
 4) THE WALL SECTION ON A2 SPECIFIES 8D COMMON NAILS FOR
 FASTENING THE ROOF SHEATHING. FBC R803.2.3.1 SHEATHING
 FASTENINGS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE
 FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6
 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. WHERE ROOF FRAMING WITH A
 SPECIFIC GRAVITY, 0.42 < G < 0.49 IS USED, SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1 . PLEASE
 REVISE.
  
 5) THE WALL SECTION ON A2 SPECIFIES BOTH FIBERGLASS AND
 ICYNENE ATTIC INSULATION. PLEASE SPECIFY ONE. FBC
 CHAPTER 13.
  
 6) THE WALL SECTION ON A2 SPECIFIES R-19 ATTIC
 INSULATION AND THE ENERGY CALCULATION FORM SPECIFIES
 R-30. PLEASE CORRECT. FBC CHAPTER 13.
  
 7) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS. ALSO SEE FBC R806.3
  
 8) THE WALL SECTION ON A2 AND FOUNDATION DETAIL ON S1
 SPECIFIES 3/4" PLYWOOD AND 2 X 12 FLOOR TRUSSES WHERE A
 CONCRETE SLAB IS SHOWN. PLEASE CORRECT. FBC R 401.2
  
 9) THE WALL SECTION ON A2 SPECIFIES FLOOR TRUSSES AT
 THE ROOF TRUSS LOCATION. PLEASE CORRECT. FBC R 802
  
 10) THE WALL SECTION ON A2 SPECIFIES ASPHALT TILES.
 PLEASE REVISE TO ASPHALT SHINGLES. DCA RULE 9B-72.
  
 11) THE MAXIMUM WINDOW AND DOOR PRESSURES ON SHEETS A1
 AND S2 DO NOT AGREE. PLEASE REVISE. SEE TABLE
 R301.2(2).
  
 12) ON SHEET S2 IMPACT PROTECTION IS SPECIFIED AS
 SHUTTERS AND PRODUCT APPROVALS ARE FOR IMPACT GLAZING.
 PLEASE CLARIFY. FBC R301.2.1.2
  
 13) THE FOUNDATION PLAN ON S1 AND THE ROOF FRAMING PLAN
 ON S2 ARE BOTH LABELED 4 ON A2. PLEASE CLARIFY.
  
 14) SPECIFY THE REQUIRED BEARING CAPACITY OF THE SOIL
 ON THE PLANS. FBC R401.2
  
 15) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 16) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORMS. FBC CHAPTER 13.
  
 17) THE ENERGY CALC. FORM INDICATES THAT THE CEILING
 FAN CREDIT IS BEING TAKEN, HOWEVER, THE PLANS DO NOT
 SPECIFY A CEILING FAN IN THE NEW GUEST BEDROOM. PLEASE
 CORRECT. SEE FBC CHAPTER 13.
  
 18) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS THAT HAVE BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. SEE DCA RULE 9B-72
 AND FBC 106.3.3* CITY AMENDMENTS.
  