| 2008-07-14 16:33:10 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SURVEY/SITE PLAN INDICATING THE DISTANCE TO |
| | PROPERTY LINES AND ADJACENT STRUCTURES. IF DISTANCES TO |
| | PROPERTY LINES ARE LESS THAN 6 FEET,SPECIFY THE |
| | DISTANCE TO STRUCTURES ON THE ADJACENT PARCELS. SEE FBC |
| | R302.1 EXTERIOR WALLS. EXTERIOR WALLS SEPARATED BY LESS |
| | THAN 6 FEET (1828 MM) SHALL HAVE NOT LESS THAN A |
| | ONE-HOUR FIRE-RESISTIVE RATING WITH EXPOSURE FROM BOTH |
| | SIDES. PROJECTIONS SHALL NOT EXTEND TO A POINT CLOSER |
| | THAN 4 FEET (1220 MM) FROM AN ADJACENT PROJECTION OR |
| | WALL. |
| | |
| | 4) THE WALL SECTION ON A2 SPECIFIES 8D COMMON NAILS FOR |
| | FASTENING THE ROOF SHEATHING. FBC R803.2.3.1 SHEATHING |
| | FASTENINGS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE |
| | FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 |
| | INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT |
| | INTERMEDIATE FRAMING. WHERE ROOF FRAMING WITH A |
| | SPECIFIC GRAVITY, 0.42 < G < 0.49 IS USED, SPACING OF |
| | RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN |
| | NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND |
| | SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1 . PLEASE |
| | REVISE. |
| | |
| | 5) THE WALL SECTION ON A2 SPECIFIES BOTH FIBERGLASS AND |
| | ICYNENE ATTIC INSULATION. PLEASE SPECIFY ONE. FBC |
| | CHAPTER 13. |
| | |
| | 6) THE WALL SECTION ON A2 SPECIFIES R-19 ATTIC |
| | INSULATION AND THE ENERGY CALCULATION FORM SPECIFIES |
| | R-30. PLEASE CORRECT. FBC CHAPTER 13. |
| | |
| | 7) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| | 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. ALSO SEE FBC R806.3 |
| | |
| | 8) THE WALL SECTION ON A2 AND FOUNDATION DETAIL ON S1 |
| | SPECIFIES 3/4" PLYWOOD AND 2 X 12 FLOOR TRUSSES WHERE A |
| | CONCRETE SLAB IS SHOWN. PLEASE CORRECT. FBC R 401.2 |
| | |
| | 9) THE WALL SECTION ON A2 SPECIFIES FLOOR TRUSSES AT |
| | THE ROOF TRUSS LOCATION. PLEASE CORRECT. FBC R 802 |
| | |
| | 10) THE WALL SECTION ON A2 SPECIFIES ASPHALT TILES. |
| | PLEASE REVISE TO ASPHALT SHINGLES. DCA RULE 9B-72. |
| | |
| | 11) THE MAXIMUM WINDOW AND DOOR PRESSURES ON SHEETS A1 |
| | AND S2 DO NOT AGREE. PLEASE REVISE. SEE TABLE |
| | R301.2(2). |
| | |
| | 12) ON SHEET S2 IMPACT PROTECTION IS SPECIFIED AS |
| | SHUTTERS AND PRODUCT APPROVALS ARE FOR IMPACT GLAZING. |
| | PLEASE CLARIFY. FBC R301.2.1.2 |
| | |
| | 13) THE FOUNDATION PLAN ON S1 AND THE ROOF FRAMING PLAN |
| | ON S2 ARE BOTH LABELED 4 ON A2. PLEASE CLARIFY. |
| | |
| | 14) SPECIFY THE REQUIRED BEARING CAPACITY OF THE SOIL |
| | ON THE PLANS. FBC R401.2 |
| | |
| | 15) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR |
| | TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | |
| | 16) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY CALCULATION FORMS. FBC CHAPTER 13. |
| | |
| | 17) THE ENERGY CALC. FORM INDICATES THAT THE CEILING |
| | FAN CREDIT IS BEING TAKEN, HOWEVER, THE PLANS DO NOT |
| | SPECIFY A CEILING FAN IN THE NEW GUEST BEDROOM. PLEASE |
| | CORRECT. SEE FBC CHAPTER 13. |
| | |
| | 18) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | STRUCTURAL WINDOW MULLIONS THAT HAVE BEEN APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. SEE DCA RULE 9B-72 |
| | AND FBC 106.3.3* CITY AMENDMENTS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |