2008-08-04 15:46:52PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.REPEAT COMMENT - INDICATE SETBACK DIMENSIONS FROM
 PROPOSED GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS
 PER SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 2.ACCORDING TO THE SURVEY THE GENERATOR WILL BE 4
 FEET FROM THE SIDE PROPERTY LINE.THE SIDE SETBACK AT
 THIS LOCATION IS 8.5 FEET.THEREFORE, THE GENERATOR
 SHALL BE A MINIMUM OF 4.5 FEET FROM THE EAST PROPERTY
 LINE TO THE FURTHEST PROJECTION POINT OF THE
 GENERATOR.
  
 3.PLEASE CLEARLY INDICATE THE SETBACK DIMENSIONS ON
 BOTH COPIES OF THE SURVEY.THE SETBACK DIMENSIONS
 SHALL BE PROVIDED FROM THE PROPERTY LINE TO THE CLOSEST
 PROJECTION POINT OF THE GENERATOR.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.