Plan Review Notes
Plan Review Notes For Permit 08060436
Permit Number 08060436
Review Stop G
Sequence Number 2
Notes
Date Text
2008-08-07 13:35:18GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. AT A MINIMUM THE GAS RISER DIAGRAM SHALL REFLECT
 WHAT IS BEING INDICATED ON THE SUBMITTED SURVEY. THE
 SUBMITTED GAS RISER DIAGRAM IS INDICATING THE GAS METER
 AS BEING INSTALLED UNDERGROUND WITH THE ONLY PIPING
 MATERIAL BENG USED AS PE. PLEASE CORRECT THE GAS
 ISOMETRIC TO INDICATE THE CORRESPONDING LENGTHS TO ALL
 CUT SECTIONS OF PIPE AS WELL AS INDICATING THE PIPING
 MATERIAL TO ALL CUT SECTIONS OF PIPE. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 ** RESPONSE NOTED, HOWEVER THE COMMENT WAS ONLY
 PARTIALLY ADDRESSED. THE RESUBMITTED GAS ISOMETRIC
 STILL IS NOT INDICATING THE CORRESPONDING LENGTHS TO
 ALL CUT SECTIONS OF PIPE. THE RESUBMITTED GAS ISOMETRIC
 IS NOW INDICATING ONLY ONE CUT SECTION OF PE PIPE @
 40'. WHAT ARE THE CORRESPONDING LENGTHS TO THE OTHER
 CUT SECTIONS OF PIPE? PLEASE KNOW THAT THE LONGEST
 LENGTH OF THE SYSTEM IS THE ADDED SUM OF ALL CUT
 SECTIONS OF PIPE FROM THE METER TO THE FARTHEST
 APPLIANCE. THE LONGEST RUN INDICATED ON THE RESUBMITTED
 PLANS IS 40', HOWEVER THIS IS WRONG DUE TO NOT ALL
 CORRESPONDING LENGTHS ARE INDICATED FOR ALL CUT SECTIOS
 OF PIPE. PLEASE ALSO KNOW THAT THE EXISTING SYSTEM IS
 UNDERSIZED PER FBC-2004 FUEL GAS CODE TABLES402.4(2)
 & 402.4(20) DUE TO THE REVISED LONGEST LENGTH OF 40'.
 THE GAS SYSTEM WILL NEED TO BE UPGRADED TO A 2 PSI
 DELIVERY PRESSURE AND SO NOTED ON THE RESUBMITTED PLANS
 WITH A CLEAR LOCATION OF THE MP REGULATORS (TWO COPIES
 OF MANUFACTURER SPECIFICATIONS OF THE MP REGULATORS
 WILL BE REQUIRED CLEARLY INDICATING THE MAKE, MODEL
 NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A
 NATIONALY RECOGNIZED TESTING LABORATORY SUCH AS CSA,
 AGA, UL). PLEASE REFERENCE THE SIZING TABLES ATTACHED
 TO THESE COMMENTS INDICATING THIS. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED PLANS ARE
 STILL NOT COMPLIANT. PLEASE REFERENCE COMMENT #1 AND
 COMPLY.
  
 5. "OK" COMMENT ADDRESSED.
  
 6. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  