| 2008-06-23 11:08:20 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE |
| | RESUBMITTED GAS ISOMETRIC RISER DIAGRAM. |
| | |
| | 1. AT A MINIMUM THE GAS RISER DIAGRAM SHALL REFLECT |
| | WHAT IS BEING INDICATED ON THE SUBMITTED SURVEY. THE |
| | SUBMITTED GAS RISER DIAGRAM IS INDICATING THE GAS METER |
| | AS BEING INSTALLED UNDERGROUND WITH THE ONLY PIPING |
| | MATERIAL BENG USED AS PE. PLEASE CORRECT THE GAS |
| | ISOMETRIC TO INDICATE THE CORRESPONDING LENGTHS TO ALL |
| | CUT SECTIONS OF PIPE AS WELL AS INDICATING THE PIPING |
| | MATERIAL TO ALL CUT SECTIONS OF PIPE. PER FBC-2004 FUEL |
| | GAS SECTION 401.1 SCOPE. |
| | |
| | 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| | BEING USED ON THE RESUBMITTED GAS ISOMETRIC.NOTE: THE |
| | TYPE OF GAS IS INDICATED ON THE PERMIT APPLICATION AND |
| | THE SURVEY, HOWEVER IT IS NOT INDICATED ON THE GAS |
| | ISOMETRIC. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: CLEARLY INDICATE THE BTU LOAD OF THE PROPOSED |
| | GENERATOR PER THE SUBMITTED PROPOSED GENERATOR |
| | MANUFACTURE SUBMITTAL SHEETS. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: REFERENCE COMMENT #1. |
| | |
| | 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | 6. THE SUBMITTED PIPE SIZING TABLES ARE WRONG PER THE |
| | FOLLOWING. |
| | NOTE: FLORIDA PUBLIC UTILITIES IS PROVIDING A 12" WC |
| | DELIVERY PRESSURE WITH A .5" WC PRESSURE DROP. THE |
| | FOLLOWING TABLES WILL BE USED FROM THE FBC-2004 FUEL |
| | GAS CODE: |
| | SCHEDULE 40 METALLIC PIPE= TABLE 402.4(2) |
| | POLYETHYLENE PLASTIC PIPE (PE)= TABLE 402.4(20) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |