Plan Review Notes
Plan Review Notes For Permit 08060436
Permit Number 08060436
Review Stop G
Sequence Number 1
Notes
Date Text
2008-06-23 11:08:20GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED GAS ISOMETRIC RISER DIAGRAM.
  
 1. AT A MINIMUM THE GAS RISER DIAGRAM SHALL REFLECT
 WHAT IS BEING INDICATED ON THE SUBMITTED SURVEY. THE
 SUBMITTED GAS RISER DIAGRAM IS INDICATING THE GAS METER
 AS BEING INSTALLED UNDERGROUND WITH THE ONLY PIPING
 MATERIAL BENG USED AS PE. PLEASE CORRECT THE GAS
 ISOMETRIC TO INDICATE THE CORRESPONDING LENGTHS TO ALL
 CUT SECTIONS OF PIPE AS WELL AS INDICATING THE PIPING
 MATERIAL TO ALL CUT SECTIONS OF PIPE. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED ON THE RESUBMITTED GAS ISOMETRIC.NOTE: THE
 TYPE OF GAS IS INDICATED ON THE PERMIT APPLICATION AND
 THE SURVEY, HOWEVER IT IS NOT INDICATED ON THE GAS
 ISOMETRIC. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: CLEARLY INDICATE THE BTU LOAD OF THE PROPOSED
 GENERATOR PER THE SUBMITTED PROPOSED GENERATOR
 MANUFACTURE SUBMITTAL SHEETS.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 6. THE SUBMITTED PIPE SIZING TABLES ARE WRONG PER THE
 FOLLOWING.
 NOTE: FLORIDA PUBLIC UTILITIES IS PROVIDING A 12" WC
 DELIVERY PRESSURE WITH A .5" WC PRESSURE DROP. THE
 FOLLOWING TABLES WILL BE USED FROM THE FBC-2004 FUEL
 GAS CODE:
 SCHEDULE 40 METALLIC PIPE= TABLE 402.4(2)
 POLYETHYLENE PLASTIC PIPE (PE)= TABLE 402.4(20)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  