| Plan Review Notes For Permit 08060414 |
| Permit Number |
08060414 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-17 08:21:28 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 230.2 NUMBER OF SERVICES | | | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED | | | BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) | | | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 | | | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND | | | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED | | | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER | | | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING | | | ONE SERVICE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|