Plan Review Notes
Plan Review Notes For Permit 08060363
Permit Number 08060363
Review Stop G
Sequence Number 1
Notes
Date Text
2008-06-17 12:08:54DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 2. MANUF. SPECIFICATION SHEETS REQUIRED FOR
 THE GAS REGULATORS. INDICATE THE MODEL
 NUMBER FOR REGULATORS. REGULATORS SHALL
 BE LISTED.
  
 3. REVISION REQUIRED FOR SHT P3.16
 INDICATING THE CORRECT INLET PRESSURE
 FROM THE METER, AND SHOWING UNIONS
 DOWNSTREAM OF THE SHUT OFF VALVES FOR
 THE REGULATORS.-PIPE SIZING SHALL BE
 CHECKED WHEN INLET PRESSURE IS
 CLARIFIED.--(REVISION SHALL BE SUBMITTED UNDER
 BUILD-COM PERMIT 05091265)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  