| Notes |
| Date |
Text |
| 2008-08-11 15:11:40 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEEDS TO BE ADDRESSED: | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE DAILY. | | | | | | 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH ACCESS TO / EGRESS FROM OTHER GUEST ROOMS OF THE | | | BUILDING. | | | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED IN GENERAL;IN PARTICULAR CHAPTER 29 - | | | EXISTING HOTELS AND DORMITORIES. | | | | | | 7.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL | | | HAVE NOT LESS THAN A 20-MINUTE FIRE-RATING. | | | | | | 8.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE | | | SELF-CLOSING AND SELF-LATCHING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|